Table C Drive Status Indicator Descriptions
#
Name
PWR
(Power)
STS
(Status)
PORT
MOD
NET A
NET B
(1)
SYNCHLINK Green
ENABLE
(1)
SynchLink LEDS are located on the SynchLink daughtercard on the main circuit board in the control cassette.
Color
State
Description
Green
Steady
Illuminates when power is applied to the drive.
Green
Flashing
Drive ready, but not running & no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable) alarm condition
exists, drive continues to run. When stopped, a start inhibit
exists and the drive cannot be started.
Steady
A type 1 (user configurable) alarm condition exists, but
drive continues to run.
Red
Flashing
A fault has occurred.
Steady
A non-resettable fault has occurred.
Red /
Flashing
The drive is in flash recovery mode. The only operation
Yellow
Alternately
permitted is flash upgrade.
Refer to the
Status of DPI port internal communications (if present).
Communication
Status of communications module (when installed).
Adapter User Manual
Status of network (if connected).
Status of secondary network (if connected).
Steady
The module is configured as the time keeper.
or
The module is configured as a follower and
synchronization is complete.
Green
Flashing
The follower(s) are not synchronized with the time keeper.
Red
Flashing
The module is configured as a time master on SynchLink
and has received time information from another time
master on SynchLink.
Green
On
The drive's enable input is high.
Green
Off
The drive's enable input is low.
Component Test Procedures
2-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 700s

Table of Contents