Installation
Terminal
TB5-4, 6-4
TB5-5, 6-5
TB5-6, 6-6
TB5-7, 6-7
Supervised Input Wiring
The supervised inputs are located on TB5, TB6, TB7 and TB8. Input 1 through Input 4
may be configured for normally open or normally closed contacts as supervised or non-
supervised. Inputs 5 and 6 are on TB8.
Table 3-3 Default Supervised Input Assignments
Terminal Position
TB7-1
TB7-3
TB7-4
TB7-6
TB8-1
TB8-3
TB 5-6, 6-6
Figure 3-7 Typical Supervised Input Wiring Diagram
The figure above shows the typical wiring for a supervised input using standard 2,200
ohm resistors. The IP-AK2 panel accepts 1,000, 2,200, 4,700, or 10,000 ohm values.
Note that both resistors must have the same value.
In addition, the Panel Tamper and External Power Fail can be supervised and capable of
being used as additional inputs if the default functionality is not needed. They also share
a single common.
10
Input Number
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7/8
Supervised input wiring must be used if Input 6 is used for "External Power
Caution
Supply AC Failed".
Wire Color
Black
Red
Variable
Variable
Default Function
Door 1 REX (Egress)
Door 1 Status
Door 2 REX (Egress)
Door 2 Status
Panel Tamper
External Power Supply AC FAIL
Reader Tamper
Wiegand Reader
Common
12VDC Power
Tamper
Buzzer