Installation; Mounting The Dg; Wiring - Honeywell krom schroder 03250831 Operating Instructions Manual

Pressure switch for gas dg..c

Advertisement

Installation

CAUTION
Please observe the following to ensure that the DG..C
is not damaged during installation and operation:
– Continuous operation with gases containing
more than 0.1 %-by-vol. H
ageing of elastomer materials and reduces the
service life.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
– Use approved sealing material only.
– Check max. ambient temperature, see
page 5 (Technical data).
– Max. inlet pressure p
– Max. test pressure for testing the entire system:
temporarily < 15 min. 2 bar (29 psig).
– Protect the appliance against dirt or moisture
(icing of condensation at subzero temperatures)
in the medium to be measured, e.g. install a filter
and ensure there is a riser.
– Avoid strong impact on the unit.
– In case of highly fluctuating pressures, install a
restrictor orifice, see page 5 (Accessories).
DG..C
▷ Installation in the vertical or horizontal position.
If installed in a horizontal position, the pre-
set switching point will change by 0.2 mbar
(0.08 "WC).
(-0.08 "WC)
=
±0 mbar
(±0 "WC)
(+0.08 "WC)
▷ If the DG..C is installed with the plug pointing
downwards, the enclosure is reduced to IP 40.
▷ The DG..C must not be in contact with masonry.
Minimum clearance 20 mm (0.79 inches).
▷ Ensure that there is sufficient installation space.
▷ For DG..VC, ensure unobstructed view of the
hand wheel.
1 Disconnect the system from the electrical power
supply.
 Shut off the gas supply.
 Purge the pipe.
4
S accelerates the
2
600 mbar (8.5 psig).
max
-0.2 mbar
=
+0.2 mbar
=
5
Mounting the DG..C..1, DG..C..9 on valVario
gas solenoid valves
4
▷ For pressure test points for inlet pressure p
interspace pressure p
select the installation position for the pressure
switch from the operating instructions of the gas
solenoid valve.
▷ Use enclosed screws only.
6

Wiring

CAUTION
Please observe the following to ensure that the
DG..C is not damaged during operation:
– If the DG..C..G (DG..VCT..G) has switched a
voltage > 24 V (> 30 V) and a current > 0.1 A
at cos φ = 1 or > 0.05 A at cos φ = 0.6 once,
the gold plating on the contacts will have been
burnt through. It can then only be operated at
this power rating or higher power rating.
– Note the switching capacity, see page 5
(Technical data).
▷ The DG..C can be connected electrically using a
tab receptacle (4.8 × 0.8 mm) or using a socket.
▷ The DG..CT is connected electrically via a socket
with ½" NPT thread and pre-wired connection
leads.
DG..C
▷ The DG..C is available as an NO contact or a
change-over contact.
▷ Observe contact position for decreasing/increas-
ing pressure control:
Change-over contact switches from NO 2 to
NC  1 for decreasing pressure control, from
NC 1 to NO 2 for increasing pressure control.
NO contact opens for decreasing pressure
control, contact closes for increasing pressure
control.
GB-3
5
or outlet pressure p
z
7
DG..C
,
u
,
d