Figure 3-6 Cabinet Wiring

Reader Wiring

Each reader port supports a single 12-volt reader with Wiegand output format. The
maximum power draw is 300 mA for readers.
To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is required. If
the optional reader buzzer feature is not needed, you can use the standard 6-conductor
cable. The cable shield should be grounded at the panel only. Grounding at both ends
can cause ground loops which can be disruptive. The maximum recommended length of
wiring is 500 feet per reader.

Table 3-2 Reader Wiring

Terminal
TB5-1, 6-1
TB5-2, 6-2
TB5-3, 6-3
Wire Color
Brown
Green
White
Honeywell
Wiegand Reader
LED Control
Wiegand Data 0 or Data
Wiegand Data 1 Or Clock
9