Disconnect Unit For Sunny Central Cp - SMA Sunny Central 250U Installation Manual

Accessories for sunny central, disconnect unit
Hide thumbs Also See for Sunny Central 250U:
Table of Contents

Advertisement

SMA America, LLC
General data
W x H x D including mounting lug for Sunny
Central 500HE‑US / Sunny Central xxxCP
Weight
Front plate of the enclosure
Width
Height
Weight
Ambient conditions
Maximum operating altitude above sea level for
nominal operation.
Operating temperature range
Temperature range for storage and transport
Maximum air humidity (condensation allowed)
8.3 Disconnect Unit for Sunny Central CP
DC connection data
Maximum array system voltage
Maximum operating current
AC connection data
Operating voltage
Operating frequency
Maximum continuous output current at 77 °F
(25 °C)
Maximum continuous output current at 122 °F
(50 °C)
Maximum continuous output power at 77 °F
(25 °C)
Installation Guide
4 ft. 11 in. x 7 ft. 3
(1,500 mm x 2,225 mm x 960 mm)
1,323 lbs. (600 kg)
3
6 ft. 2 
 in. (1,900 mm)
4
1
4 ft. 7 
 in. (1,400 mm)
8
100 lbs. (46 kg)
6,500 ft. (2,000 m)
− 13 °F ... +122 °F
( − 25 °C ... +50 °C)
− 40 °F ... +122 °F
( − 40 °C ... + 60 °C)
1000 V
1,400 A
324 V ... 396 V
50/60 Hz
1411 A
1283 A
880 kVA
DisconACDC_SCUS-IUS103110
8  Technical data
1
1
 in. x 3
 ft.
2
8
95 %
67

Advertisement