3. Installation
3.4 Mechanical Mounting
p Mount the MBP (on the UPS, on the EBM, in the rack or on the wall), see 2.1.
3.5 Installation requirements
Recommended protective devices and cable cross-sections
1. Recommended upstream protection
Refer to the UPS User Manual for circuit breaker current rating.
The circuit breaker has to be installed upstream the MBP Normal AC source.
2. Recommended cable cross-sections
MBP6K208
MBP11K208
with
8kVA UPS
MBP11K208
with
11kVA UPS
Copper wire, solid or stranded.
Page 10
Terminal
Wire
position
function
L1
Phase
L2
Phase
Ground
L1
Phase
L2
Phase
Ground
L1
Phase
L2
Phase
Ground
Terminal wire
Minimum input wire
size rating
0.5-10 mm
6 mm
2
(20-8 AWG)
10 mm
4-25 mm
10 mm
2
(12-4 AWG)
16 mm
4-25 mm
16 mm
2
(12-4 AWG)
25 mm
Tightening
size rating
(10 AWG) 105°C
2
10 lb in
(8 AWG) 75°C
2
(8 AWG) 105°C
2
18 lb in
(6 AWG) 75°C
2
(6 AWG) 90°C
2
18 lb in
(4 AWG) 75°C
2
torque
SK-90610-Y4_EN