Veichi SI23-D1 series Manual page 15

Solar water pump inverter
Table of Contents

Advertisement

Binding
Keyboard
F00.08
digital setting
frequency
Max
F00.09
frequency
Upper limit
frequency
F00.10
source
selection
Upper
frequency
F00.11
limit digital
setting
Lower limit
F00.12
frequency
Lower limit
F00.13
frequency
running mode
F00.14
ACC time 1
F00.15
DEC time 1
Rotary
F00.16
direction
selection
LED"000"digit: communication command instruction
binding
LED"0000"digit: optional card command instruction
binding
0 : no binding
1 : keyboard number given frequency
2 : Reserved
3 : Voltage/Current analog AI1 given
4 : Voltage/Current analog AI2 given
5 : Reserved
6 : Terminal pulse PUL given
7: RS485 communication given
8 : Terminal UP/DW control
9 : PID control given
A: Program control (PLC) given
B: Optional card
C: Multi-steps speed given
0~upper limit
upper limit~600.00Hz
0: Upper limit frequency digital given
1: Reserved
2: Voltage/Current analog AI1 give
3: Voltage/Current analog AI2 given
4: Reserved
5: Terminal pulse PUL given
6: RS485 communication given
7: Optional card
Lower limit frequency~max frequency
0.00~upper limit frequency
0: Stop output, enter into pause running state
1: Run at lower limit frequency
0.01~650.00s
0.01~650.00s
LED"0"digit: running direction takes the opposite
0: Direction unchanged
1: Direction takes the opposite
LED"00"digit: running direction prohibited
0:Forward and reverse commands are allowed
1: Only FWD command allowed
2: Only REV command allowed
LED"000"digit: frequency control direction selection
SI23 Solar Pump Inverter Manual
15
50.00Hz
0x008
50.00Hz
0x009
0
0x00A
50.00Hz
0x00B
0.00Hz
0x00C
1
0x00D
20.00s
0x00E
20.00s
0x00F
0000
0x010

Advertisement

Table of Contents
loading