electrical components. Such operation would invalidate
any applicable Bryant warranty.
NOTE: Check all factory and field electrical connections
for tightness.
Convenience Outlets —
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock- - out and tag- - out this switch, if necessary.
Two types of convenience outlets are offered on 551J models:
Non- - powered and unit- - powered. Both types provide a
125- - volt GFCI (ground- - fault circuit- - interrupter) duplex
receptacle rated at 15- - A behind a hinged waterproof access
cover, located on the end panel of the unit. See Fig. 21.
Convenience
Outlet
GFCI
Pwd-CO
Fuse
Switch
Fig. 21 - - Convenience Outlet Location
Installing
Weatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover cannot
be factory-mounted due its depth; it must be installed at unit
installation. For shipment, the convenience outlet is covered
with a blank cover plate.
The weatherproof cover kit is shipped in the unit's control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT
ALL
CONVENIENCE OUTLET. LOCK- - OUT AND TAG- - OUT
ALL POWER.
Pwd-CO
Transformer
Control Box
Access Panel
Cover:
A
weatherproof
POWER
TO
UNIT
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until
approximately
exposed. Press the gasket over the screw heads. Slip the
backing plate over the screw heads at the keyhole slots
and align with the gasket; tighten the two screws until
snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as
shown in Fig. 22. Remove two slot fillers in the bottom of
the cover to permit service tool cords to exit the cover.
Check for full closing and latching.
COVER – WHILE-IN-USE
WEATHERPROOF
Fig. 22 - - Weatherproof Cover Installation
Non- - powered type: This type requires the field
installation of a general- - purpose 125- - volt 15- - A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125- - v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit- - powered type: A unit- - mounted transformer is
factory- - installed to stepdown the main power supply
voltage to the unit to 115- - v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
C08128
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit's control
box access panel. See Fig. 21.
The primary leads to the convenience outlet transformer are
not factory- - connected. Selection of primary power source is
a customer- - option. If local codes permit, the transformer
primary leads can be connected at the line- - side terminals on
the unit- - mounted non- - fused disconnect switch; this will
provide service power to the unit when the unit disconnect
switch is open. Other connection methods will result in the
convenience outlet circuit being de- - energized when the unit
disconnect switch is open. See Fig. 23.
AND
17
1
/
-in. (13 mm) under screw heads are
2
RECEPTACLE
NOT INCLUDED
BASE PLATE FOR
GFCI RECEPTACLE
C09022