Step 9 - Install External Condensate Trap And Line; Step 10 - Make Electrical Connections; Field Power Supply - Bryant 551J*07A/G Series Installation Instructions Manual

Single package rooftop cooling only sizes 07, 08, 09, 11 and 12 with puronr (r--410a) refrigerant
Table of Contents

Advertisement

5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel
and the hood top.
7. Replace the filter access panel.
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 13 - - Economizer Filter Installation
Step 9 — Install External Condensate Trap and Line
3
The unit has one
/
-in. condensate drain connection on
4
the end of the condensate pan and an alternate connection
on the bottom. See Fig. 14. Unit airflow configuration
does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal
applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do this
before setting the unit in place. The red drain pan plug can
1
be tightened with a
/
- - in. square socket drive extension.
2
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a
square socket drive extension) and install it in the side
drain connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
DRAIN
SIDE DRAIN
(FACTORY-INSTALLED)
Fig. 14 - - Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 15.
OUTSIDE
AIR
HOOD
FILTER
FILTER
CLIP
C08634
1
/
- - in.
2
ALTERNATE
PLUG
BOTTOM DRAIN
C08021
MINIMUM PITCH
1˝ (25 mm) PER
BASE RAIL
10´ (3 m) OF LINE
OPEN
VENT
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4 in. (102 mm) trap is recommended.
Fig. 15 - - Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away from
the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use
a pipe size smaller than the unit connection (
Step 10 — Make Electrical Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground
may consist of electrical wire connected to unit ground
lug in control compartment, or conduit approved for
electrical ground when installed in accordance with
NEC; ANSI/NFPA 70, latest edition (in Canada,
Canadian Electrical Code CSA [Canadian Standards
Association] C22.1), and local electrical codes.
NOTE:
Field- - supplied wiring shall conform with the
limitations of minimum 63_F (33_C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet: The
power source leads to the convenience outlet's transformer
primary are not factory connected. Installer must connect
these leads according to required operation of the
convenience outlet. If an always- - energized convenience
outlet operation is desired, connect the source leads to the
line side of the unit- - mounted disconnect. (Check with local
codes to ensure this method is acceptable in your area.) If a
de- - energize via unit disconnect switch operation of the
convenience outlet is desired, connect the source leads to the
load side of the unit disconnect. On a unit without a
unit- - mounted disconnect, connect the source leads to
compressor contactor C and indoor fan contactor IFC
pressure lugs with unit field power leads (see Fig. 16).
14
3˝(76 mm)
MIN
SEE NOTE
ROOF
CURB
DRAIN PLUG
a50--- 9660
3
/
-in.).
4

Advertisement

Table of Contents
loading

Table of Contents