Step
Work Description
Rotate switch base shaft counter-clockwise to put
switch blades in open/OFF position. Place
21
insulator on mechanism. *Insulators used only on
60 amp models.
Align base mounting holes and install 3 screws
22
with 5/16" driver. (1 on top, 2 on bottom) Torque
to 20 to 25 in-lbs.
Align fuse base and install 2 mounting screws with
23
5/16" driver. Torque to 20 to 25 in-lbs.
For fusible switches reinstall insulator and and
retainer screw with 1/4" driver. The right side of
the insulator wraps around the switch base wall as
24
shown. Torque to 20 to 30 in-lbs. Insulator used
only on 60 amp and 30 amp Canadian models.
For fusible switches position load side fuse clip
25
connector onto the locator tabs and fasten with
screw using 1/4" driver. Torque to 20-30 in-lb.
Revision : 1
x2
5 of 8
Reference Pictures & Comments
LOCATORS