Switch base replacement. 3-pole, 30/60 amp fusible safety switches.

Advertisement

Step
Work Description
If equipped with a neutral or control pole, loosen
mounting screw with 5/16" driver and slide to the
10
left. Screw is captivated by plastic base and does
not need removed.
Mark the line side lugs before removing so they
11
can be reinstalled back in their original phase
locations.
Remove screws from line side lugs using 5/16"
12
driver. Move wires to the side for base removal.
Keep screws for reinstallation on new base.
Remove switch base with 5/16 driver. (3 screws, 2
13
on bottom, 1 on top) Keep screws for
reinstallation on new base.
Slide base to left to disengage shaft from
mechanism. Remove insulator. Keep insulator if
14
present for reinstallation on new base. Insulator
used only on 60 amp models.
Revision : 1
x2
x3
3 of 8
Reference Pictures & Comments