Download Print this page

Eaton ECN16A Replacement Instructions Manual page 6

Switch base replacement. 3-pole, 30/60 amp fusible safety switches.

Advertisement

Step
Work Description
Remove arc shield mounting screw with 1/4"
26
driver. Remove arc shield. Keep screw and arc
shield for reinstallation.
Reattach line side lugs using 5/16" driver. Torque
27
to 20-30 in-lbs.
If device has a neutral or control pole, reinstall.
Note : Two nibs on the side fit into notches on the
28
side of the base. Tighten mounting screw to 20 to
25 in-lbs.
29
Reattach arc shield. Torque to 20-30 in-lbs.
Revision : 1
x1
x3
NIB
NIB
x1
6 of 8
Reference Pictures & Comments

Advertisement