14.2 Communication module Web, Adv. Web

The communication module is used to activate the advanced web functionality of the processing unit.
It is therefore called Advanced Web module, Adv.Web.
The Adv Web module has the following characteristics:
built-in WindowsCE® platform with web server application
generic tree structure to read and write data points
platform for programming web applications
alarm server for SMS/E-mail
peer to peer communications, no server required
full modem RS-232 port
GSM/GPRS support
calling functions.

14.2.1 Services associated with Adv Web

The following services require Adv Web:
IQAlarm 100
IQReport

14.3 Communication module BacNet IP

The communication module BacNet IP connects the processing unit to a BacNet IP
network.
The BacNet IP module has the following characteristics:
integration for building automation systems via BacNet IP
client communication to other BacNet units
pre-installed generic BacNet server
supports BacNet/IP (B-AAC-profile and BBMD)
network parameters are configured through the processing unit, HMI or
SCOPE

14.4 Communication module ModBus

The ModBus communication module connects the processing unit to a ModBus
network, for reading sensors. The ModBus module can be upgraded using an SD card.
The ModBus module has the following characteristics:
integration to a building automation system via RS 485 ModBus RTU
two ModBus slave communication ports
galvanic ally isolated connection to the ModBus network.

14.5 Module MBus

The MBus module is used to map the necessary data points from the MBus units to the
processing unit.
The MBus module has the following characteristics:
The MBus network operates the MBus module such as MBus master and
periodically asks for data points from the MBus units.
MBus mapping of the MBus module defines all MBus units and their required data
points (bonds) that will be integrated and mapped to the processing unit
Up to 6 MBus units such as heating, water or electricity meters, can be connected
directly to the MBus module (up to 64 MBus units with MBus amplifiers)
Up to 200 data points (bonds) can be defined in the MBus mapping
Connecting the MBus module to the MBus network is galvanic ally separated by
optocouplers. The bus power supply is short circuit proof:

14.5.1 Services associated with MBus

The following services require MBus
IQMeter200
42