IQHeat
User manual
4 Log in and set the clock
4.1
Password and login
The controller has password protection, allowing access to different menus.
NOTE: For security reasons must the factory set password be changed the first time the IQHeat starts up.
The following log-in levels are available:
All users: no log-in, no password required
•
read access to all menus except the system parameters, configuration and detail menus
•
read access to alarm lists and alarm history
End user, level 6, password 1000
•
appears with one key in the upper left corner of the display
•
all rights as for in "all users"
•
read access to all menus except configuration menus
•
write access to the main set points (Setpoints/Settings. > Setpoints)
•
alarms and alarm history can be acknowledged and reset
Service level, level 4, password 2000
Used for configuring I/Os and system settings. Only qualified service personnel should make changes at this
level.
•
appears with two keys in the upper left corner of the display
•
all rights as for "End users"
•
access to all menus except I/O configuration and system settings
OEM, level 2
•
appears with three keys in the upper left corner of the display
•
all rights as for System Administrator
•
access to all menus and system settings.
Contact Cetetherm if there is a need to change anything at this level.
4.1.1
Log in
1. Keep the OK button pressed to access the
Password menu.
2. The first digit of four is marked with 0.
3. Turn the navigation dial until the desired number
appears.
4. Press OK to proceed to the next digit, continue
until all four are entered correctly and press OK.
The current key symbol will appear in the upper left
corner of the display window
10
.