Publication 1756-In596A-En-P - December - Allen-Bradley ControlLogix 1756-PA75/B Installation Instructions Manual

Table of Contents

Advertisement

16
ControlLogix Power Supplies
Cat. No.
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Vibration
Operating Shock
Non-operating Shock
Emissions
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Oscillatory Surge Withstand
Enclosure Type Rating

Publication 1756-IN596A-EN-P - December 2004

1756-PA75/B
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
-40 to 85°C (-40 to 185°F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing
IEC 60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
CISPR 11:
Group 1, Class A
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
IEC 61000-4-4:
±4kV at 5kHz on power ports
IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
IEEE C37.90.1:
3kV
None (open-style)
1756-PB75/B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controllogix 1756-pb75/b

Table of Contents