Siemens CP 343-1 User Manual page 31

S7-cps for industrial ethernet
Hide thumbs Also See for CP 343-1:

Advertisement

Transfer the process inputs (DB10) to the I addresses with PNIO_SEND
For the configured I addresses, you will need to make data areas available on the
PROFINET IO device, for example in a DB (in this example in a DB10) that
contains not only the process data but also the data areas for the IOCS status
information.
Figure 6-7
Data Structure for PNIO_SEND in the PROFINET IO Device
The call interface PNIO_SEND in the user program
STL
call fc 11
CPLADDR:=
W#16#0100
LEN
:=
20
IOCS
:=
P#DB10.DBX20.0 BYTE 3
DONE
:=
M 70.0
ERROR
:=
M 70.1
STATUS :=
MW 72
CHECK_IOCS := M 70.2
SEND
:=
P#DB10.DBX0.0 BYTE 20
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
6 Configuring and Programming the CP as a PROFINET IO Device
Explanation
//PNIO_SEND block call
//(transfer inputs to IO controller)
//Module address from hardware configuration
//No. of log. I addressesto transfer. in bytes
//Per send data byte, one bit status in DB10
//Address for return parameter DONE
//Address for return parameter ERROR
//Address for return parameter STATUS
//Address for return parameter CHECK_IOCS
//Data area to be transferred from DB10
//(20 bytes)