Electrical parameters of the RS 485 LAN cables
You can use the following cables to attach an RS 485 bus segment and individual DTEs to the PROFIBUS ILM:
â
Cable Type A complying with PROFIBUS DP; (DIN 19 245 Part 2)
â
Cable Type B complying with DIN 19 245 Part 1; 04.91; Section 3.1.2.3
Remember the restricted distance and transmission rate possible with the Type B cable (according to Table 2).
Cable Parameters
Characteristic resistance
Capacitance per unit
length
Loop resistance
Core diameter
Core cross-section
Table 5:
Electrical Parameters of the Shielded Twisted Pair LAN Cables
Type A
Type B
135 to 165 ohms
100 to 130 ohms
(3 to 20 MHz)
(f
100 kHz)
<30 pF/m
<60 pF/m
<110 Ohms/km
0.64 mm
0.53 mm
2
0.34 mm
0.22 mm
51