Quick Start for Experienced Users
Configure the system.
6.
Set up your system I/O configuration for the particular slot in which you installed the scanner (slot 1 in
this example). If using APS software, select the 1747 scanner from the list of modules. If it is not
listed in your software version, select Other and enter the scanner input module ID code (13608)
at the prompt on the I/O configuration display.
(Additional information about how to use Allen Bradley's Advanced Programming Software [APS] to
configure your system can be found in the APS User Manual, Publication 9399 APSUM.)
Example of Software Prompt:
Press ENTER to select I/O Module
Enter Module ID Code> 13608
offline
SLC 5/02
SELECT
MODULE
F2
Enter the number of scanned words.
7.
Enter the number of Scanned Input and Output Words using the Specialty I/O and Advanced Setup
menus. The default value is 32 I/O words. You can specify less than 32 and reduce the processor
scan time by transferring only the part of the input and output image that your application requires. It
is important that you do not set either of these values to 0. If you do, the scanner will not work
correctly.
(Additional information about how to use Allen Bradley's Advanced Programming Software [APS] to
configure your system can be found in the APS User Manual, Publication 9399 APSUM.)
Publication 1747 6.6 - July 1996
File EXAMPLE
Reference
Chapter 4
(Configuration and
Programming)
your
programming
software's user
manual
Reference
Chapter 4
(Configuration and
Programming)
your
programming
software's user
manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents