Example Discrete I/O Throughput with Block Transfers Present

An SLC 5/03 is using a scanner to control a 115.2K baud RIO link
that has 3 adapters and 4 logical devices.
Adapter #1 (1747-ASB module):
starting logical rack 0, logical group 0
12 logical groups (1 1/2 logical racks)
one 8 word and two 4 word BT write/read modules in logical rack 0
one 2 word BT write/read module in logical rack 1
Adapter #2 (1771-ASB module):
starting logical rack 2, logical group 0
2 logical groups (1/4 logical rack)
one 64 word BT write/read module
Adapter #3 (1771-ASB module):
starting logical rack 2, logical group 2
2 logical groups (1/4 logical rack)
one 32 word BT write/read module
1. Use the throughput formula to calculate the maximum throughput
of the 1747-ASB module.
T
= 2T
+ 2T
dm–bt
ps
RIO
T
= 25.0 ms, which is from the APS reference manual (assume for
ps
example)
T
= The total RIO scan time (ms)
RIO
T
= Additional time due to sending any BT data on the RIO link
btx
T
= Two 1747-ASB module backplane scan times (calculated from
adp
ASB
manual) = 2(4.5) = 9.0 ms
T
= 22.0 ms from the table on page A–13, T
SNo–bt
Transfers
(Normal Mode). There are 3 logical racks configured.
T
= 5.0 ms
SNi
T
= 10.0 ms, which is from I/O module instruction sheets
id
T
= 1.0 ms, which is from I/O module instruction sheets
od
T
= 2(25.0) + 2T
dm–bt
RIO
+ 2T
+ T
+ T
+ T
btx
adp
SNo–bt
+ 2T
+ 9.0 + 22.0 + 5.0 + 10.0 + 1.0
btx
+ T
+ T
SNi
id
od
with Block
SNo