Allen-Bradley ControlLogix 1756-OV32E Installation Instructions Manual page 16

Dc 10-30v electronically-fused sinking current output module
Hide thumbs Also See for ControlLogix 1756-OV32E:
Table of Contents

Advertisement

16 ControlLogix DC (10-30V) Electronically-Fused Sinking Current Output Module
Environmental Conditions
Operational
Temperature
Storage Temperature
Relative Humidity
Vibration
Operating Shock
Non-operating Shock
Emissions
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Publication
1756-IN582A-EN-P - August 2003
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
-40 to 85°C (-40 to 185°F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing
IEC 60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
CISPR 11:
Group 1, Class A
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
IEC 61000-4-3:
20V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz
IEC 61000-4-4:
±4kV at 2.5kHz on power ports
±4kV at 2.5kHz on signal ports