Advertisement

5. Remove the protective backplane cap as shown in "Remove the Protective
Caps" on page 10.
6. Once attached to the DIN rail, slide modules to the left to mate with the
repeater adapter or another repeater module.
ATTENTION
!
IMPORTANT
IMPORTANT
7. Connect the fiber cable as shown in "Connect the Fiber Cable" on page 13.
ControlNet Modular Repeater Medium Distance Fiber Module
Be certain that the adapter and repeater modules are secured
together with DIN rail anchors. Failure to do so may result in
the loss of communications and/ or cause damage to the
modules. The total number of modules that can be attached to
the repeater adapter can not exceed four or the total power
consumption of the modules can not exceed 1.6A @ 5VDC,
whichever comes first.
If you exceed the module or power limit, you may cause
damage to the repeater adapter and modules.
If this is the right–most module, a DIN rail latch must be used
on the right side of the fiber module.
Publication 1786-IN011B-EN-P - October 2000
9
30043-M