Allen-Bradley MicroLogix 1200 Installation Instructions Manual page 14

Analog output module
Hide thumbs Also See for MicroLogix 1200:
Table of Contents

Advertisement

14
MicroLogix™ 1200 Analog Output Module
Configuration Data File
The configuration of the format for analog outputs is made at going to run (GTR). Changes
made to the configuration file while in run mode have no effect.
The configuration table for analog outputs is shown in the table below.
Configuration Data File
15
14
13
Data Format
0
Output Channel 0
Data Format
1
Output Channel 1
Data Format
2
Output Channel 2
Data Format
3
Output Channel 3
4
5
6
7
Bit 15 and Bits 7 through 0 - Reserved
These bits are reserved and are not checked by the module.
Data Format (Bits 14 through 12)
These bits indicate the format of the data as shown in the following table. Other
combinations of these bits are not supported and result in an error.
Bit Settings
14
13
0
0
0
1
other
Publication 1762-IN016A-EN-P - July 2003
12
11
10
9
Type/Range Select
Output Channel 0
Type/Range Select
Output Channel 1
Type/Range Select
Output Channel 2
Type/Range Select
Output Channel 3
12
0
0
Bit Position
8
7
6
5
reserved
reserved
reserved
reserved
Data Format
Raw/Proportional
Scaled for PID
Not Supported
4
3
2
1
reserved
reserved
reserved
reserved
0