Allen-Bradley MicroLogix 1200 Installation Instructions Manual page 13

Analog output module
Hide thumbs Also See for MicroLogix 1200:
Table of Contents

Advertisement

Output Data File
For each module, slot x, words 0 through 3 contain the channel output data.
Raw/Proportional Format
15
14
13
0
0
1
0
2
0
3
0
Words 0 through 3 contain the analog output data for channels 0 through 3, respectively. The
module ignores the "don't care" bits (0 through 2), but checks the sign bit (15). If bit 15
equals 1, the module sets the output value to 0V or 0 mA.
Scaled-for-PID Format
15
14
13
0
0
0
1
0
0
2
0
0
3
0
0
Words 0 through 3 contain the analog output data for channels 0 through 3, respectively. The
module ignores the "don't care" bits (0 and 1), but checks the sign bit (15), and bit 14. If bit
15 equals 1, the module sets the output value to 0V or 0 mA. If bit 15 equals zero and bit 14
equals 1, the module sets the output value to 10.5V dc or 21 mA.
Bit Position
12
11
10
9
Channel 0 Data 0 to 32,760
Channel 1 Data 0 to 32,760
Channel 2 Data 0 to 32,760
Channel 3 Data 0 to 32,760
Bit Position
12
11
10
9
Channel 0 Data 0 to 16,380
Channel 1 Data 0 to 16,380
Channel 2 Data 0 to 16,380
Channel 3 Data 0 to 16,380
MicroLogix™ 1200 Analog Output Module
8
7
6
5
8
7
6
5
AB Spares
Publication 1762-IN016A-EN-P - July 2003
4
3
2
1
0
0
0
0
0
0
0
0
4
3
2
1
0
0
0
0
13
0
0
0
0
0
0
0
0
0
0

Advertisement