8. Select the method which the inverter uses to measure the data of the connected motor:
9. The quick commissioning completes when the following window appears. You can select
to go to the JOG page immediately or later.
SINAMICS G120 Smart Access
Operating Instructions, 04/2018, A5E43332487
①
Motor data is not measured.
②
(Recommended): Measure the motor data at standstill and with the motor rotating. The in-
verter switches off the motor after the motor data identification has been completed.
③
Measure the motor data at standstill. The inverter switches off the motor after the motor data
identification has been completed. Select this setting if the motor cannot freely rotate, for
example, for a mechanically limited traversing range.
④
Measure the motor data with the motor rotating. The inverter switches off the motor after the
motor data identification has been completed
⑤
②
Setting same as
. The motor accelerates to the currently set setpoint after the motor data
identification.
⑥
③
Setting same as
. The motor accelerates to the currently set setpoint after the motor data
identification.
Standard Web pages
5.4 Quick commissioning
33