Potentiometer R310; Analog Outputs - Advanced Energy Thyro-Power Manager Operating Instructions Manual

Table of Contents

Advertisement

T0[s] (50Hz):
T0[Periods]:
0.2
10
0.4
20
0.6
30
0.8
40
1
50
1.2
60
1.4
70
1.6
80
1.8
90
2
100
4
200
6
300
8
400
10
500
15
750
20
1000
25
1250
30
1500
Table 13: Output possibilities at the analog output terminals
The T0 time (in PC mode) can be set easily and precisely via the help of the PC program
or via the bus system.

7.5. POTENTIOMETER R310

If the Thyro-Power Manager is configured without a PC program and bus system (S1.8
OFF), the limiting value for network load optimization and for the three converter inputs can
thus be set via Poti R310. The standard default setting is 200% and the Poti is turned to its
right-hand blocked position. The same limiting value is used for all three inputs per Poti. A
unique limiting value can be determined for each one of the 3 converters via a PC program
or via the bus system (in PC mode).
As the potentiometer does not possess a scale, one can deploy analog output 6 (X8.1 /
X8.2) as help for the setting (connect the voltmeter, range 0 – 10V). If the potentiometer is
changed, (no PC mode) the analog output is automatically switched over to the output of
41
Analog[V]:
0,5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.36
5.71
6.07
6.43
7.32
8.21
9.11
10
42
the potentiometer value. In the course, meaning here 5V = 100% (type value of converter),
the adjustment interval ranges between 0 – 200% (0 – 10V).
In PC mode (S1.8 = closed), the switches and potentiometer settings are
mostly ignored and only those values are used, which are stored and set via a
PC program. In this case, a potentiometer change e.g. does not incur a change
of values and the setting help is not activated!

7.6. ANALOG OUTPUTS

The Thyro-Power Manager possesses six analog output terminals (0 – 10V). Different
values may be read out from them (see also chapter 4.5.4.4 for this).
The following values may be read out:
Value:
Effective value converter 1
Effective value converter 2
Effective value converter 3
Mains voltage
Analog input 1
Analog input 2
Poti R309
Poti R310
Temperature
Bus value 1
Bus value 2
Bus value 3
Bus value 4
Bus value 5
Bus value 6
Table 14: Output options at the analog output terminals
However, the desired output value can only be set via a PC program or bus system. The
standard default setting is as follows:
Output:
10V = 100% = Type value of converter (at
1V~)
10V = 100% = Type value of converter (at
1V~)
10V = 100% = Type value of converter (at
1V~)
10V = 100% = 230V~ or 115V~
10V = 100% = 10V / 5V / 20mA
10V = 100% = 10V / 5V / 20mA
Setting help: see chapter 7.4
Setting help: 5V = 100% (Type value of
converter)
10V = 100
10V = 4096
10V = 4096
10V = 4096
10V = 4096
10V = 4096
10V = 4096