Figure 9: Connection diagram for power and energy measurement
An AEG voltage converter (order no. 2 000 000 399) can be deployed as voltage
transformer. This device possesses a transformer ratio of 16:1, and can primarily be used up
to 690V. If this converter is deployed, the following series resistance values result:
Mains
Secondary
voltage
voltage. [V]
[V]:
1100
6,8755
2300
14,3755
4000
25
5000
31,255
6900
43,1255
Table 3: Series resistance values for AEG voltage converter

4.5.4.4. CONNECTION FOR ANALOG OUTPUTS

All measurement values may be read from one (or more) of the six analog outputs (0 –
10V).
Series resistance [Ohm]:
Calculated
Selected:
Note:
:
44298
44000
22k + 22k
100848
101000
100k + 1k
180961
181000
180k + 1k
228087
228200
220k + 8k2
317625
320000
220k + 100k
19
20
Standard setting:
Output no.:
1
2
3
4
5
6
Table 4: Standard output values for analog outputs
Terminals
Standard output:
X7.1 / X7.2
Converter 1
X7.3 / X7.4
Converter 2
X7.5 / X7.6
Converter 3
X7.7 / X7.8
Mains voltage
X7.9 / X7.10
Temperature
X8.1 / X8.2
Bus value 6 / adjustment
support
Figure 10: Connection diagram for analog outputs