Connection Of Analog Ac Inputs; Shut Down, Disassembly; Safety Notes; Electro Terminals - Advanced Energy Thyro-Power Manager Operating Instructions Manual

Table of Contents

Advertisement

Figure 13: Connection diagram for analog DC inputs
Note:
The initial value of the analog inputs can be increased to 4mA (and 1V or 2V, respectively)
by deploying the dip-switch S1.7.
This is necessary if e.g. a range interval of 4- 20mA is desired.

4.5.4.8. CONNECTION OF ANALOG AC INPUTS

If the unit is not deployed for network peak-load monitoring, but as I/O module, the 3
transformer inputs at the terminal X5 may be used as analog AC inputs. The measurement
range interval is 0 – 1V~.
23
24
Figure 14: Connection diagram of analog AC inputs

5. SHUT DOWN, DISASSEMBLY

Shutdown and disassembly of the unit may be performed for the reason of venue change or
for disposal purposes.

5.1. SAFETY NOTES

The following 5 safety rules must be complied with, prior to the beginning of all work performed
to the unit:

5.2. ELECTRO TERMINALS

For disassembly, perform the following steps:
1. Separate the Unit from the voltage supply 230V~, respectively 110V~.
2. Separate all other connections.
Electrical connections are thus disassembled
Attention Mains Voltage!
Safety rules for work performed to electrical facilities:
1. Disconnect equipment from the mains (establish a voltage free status)
2. Secure equipment against re-activation
3. Determine voltage free status of equipment by measurement
4. Ground and short-circuit equipment
5. Cover or establish borders to neighboring parts under voltage