Problems, Causes, and Solutions
PROBLEM
Plants are too dry
Plants are too wet
Moisture level seems incorrect
Moisture always at max or minimum
Alarm symbol is displayed
Module display is blank
For more detailed information, application notes, or assistance, please visit us at www.hunterindustries.com.
CAUSE
•
Moisture level setting too low
•
Sensor in wrong location
•
Moisture level setting too high
•
Sensor in wrong location
•
Pause mode has been set
•
Incorrect sensor installation/placement
•
Failed sensor
•
Module failure
•
Power failure
Troubleshooting Guide
SOLUTION
•
Increase arrows (+ button)
•
Move sensor or valve wires; sensor must be
in last zone to water
•
Decrease arrows (- button)
•
Move sensor to a sunnier location
•
Turn off Pause
•
Ensure full soil contact with sensor
•
Check sensor wiring
•
Use handheld sensor meter to verify
operation
•
Replace module (part no. SC-MOD)
•
Check power connection to host controller