Mitsubishi Electric MELSEC-I/OLINK Handbook page 70

Transition
Table of Contents

Advertisement

6
REPLACING THE I/O MODULES
Specifications
Operation indicator
24-point terminal block (M3 screw)
External wiring method
Transmission circuit included
Applicable wire size
Applicable crimping
terminal
Voltage
I/O module
power
supply
Current
External dimensions
50(H) × 114(W) × 66(D) mm
Installation method
Weight
6
- 37
AJ55TB32-8DT
ON indication (LED)
2
(when the following applicable crimping
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
15.6 to 27.6VDC
50mA
Screw mounted
Mounted to DIN rail
0.3kg
A20XB-16UD
ON indication (LED)
40-point terminal block (M3 screw)
Transmission circuit included
2
0.3 to 1.25mm
2
terminals are used: 0.75 to 2mm
)
2
For wire sizes 0.75 to 2mm
R2-3SL, RAV2-3SL, RAP2-3SL,
VD2-3S, VD2-3.5SS, VD2-3.5S,
VDAV2-3.5SS, VDAV2-3.5S
21.6 to 27.6VDC
(ripple voltage 0.5Vp-p or less)
106mA
40(H) × 190(W) × 60(D) mm
Screw mounted
Mounted to DIN rail
0.3kg
Compat-
Precautions for
ibility
replacement
Wiring must be changed.
Existing wires can be used but
applicable crimping terminals
are different.
For details, refer to Section
6.3.
Operating voltage range is
different.
Because the current
consumption has increased,
the current capacity must be
reviewed.
The shape is different.
Because mounting hole size is
×
different, reworking is
required.
The A20XB-16UD can be
mounted to the existing DIN
rail.