Mitsubishi Electric MELSEC-I/OLINK Handbook page 64

Transition
Table of Contents

Advertisement

6
REPLACING THE I/O MODULES
Specifications
Operation indicator
External wiring method
Transmission circuit included
Applicable wire size
Applicable crimping
terminal
Voltage
Ripple voltage 4Vp-p or less
External
power
supply
Current
(24VDC TYP. all points ON)
Voltage
I/O module
power
supply
Current
External dimensions
50(H) × 177(W) × 66(D) mm
Installation method
Weight
6
- 31
AJ55TB32-16DR
A20SB-08UD
ON indication (LED)
30-point terminal
40-point terminal block
(M3 screw)
Transmission circuit
2
(when the following applicable crimping
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
24VDC ± 10%
45mA
15.6 to 27.6VDC
70mA
40(H) × 140(W)
Screw mounted
Mounted to DIN rail
0.4kg
: Compatible,
A20PB-08RS
ON indication (LED)
30-point terminal
block
block
(M3 screw)
(M3 screw)
Transmission circuit
included
included
2
0.3 to 1.25mm
2
terminals are used: 0.75 to 2mm
)
2
For wire sizes 0.75 to 2mm
R2-3SL, RAV2-3SL, RAP2-3SL,
VD2-3S, VD2-3.5SS, VD2-3.5S,
VDAV2-3.5SS, VDAV2-3.5S
21.6 to 27.6VDC
(ripple voltage 0.5Vp-p or less)
117mA
104mA
40(H) × 140(W)
× 60(D) mm
× 60(D) mm
Screw mounted
Mounted to DIN rail
0.18kg
0.2kg
: Partially changed, ×: Not compatible
Compat-
Precautions for
ibility
replacement
Wiring must be changed.
Existing wires can be used but
applicable crimping terminals
are different.
For details, refer to Section
6.3.
External power supply for the
A20SB-08UD is unnecessary.
The A20PB-08RS external
power supply and the I/O
module power supply are
shared.
Operating voltage range is
different.
Because the current
consumption has increased,
the current capacity must be
reviewed.
The shape is different.
×
A mounting space for two
modules is required.
Because mounting hole size is
×
different, reworking is
required.
The A20SB-08UD and
A20PB-08RS can be mounted
to the existing DIN rail.
Be careful about the mounting
dimensions as two modules
are required.