VIPA System 300S
6.4.4.3
FC 03 - Read Output Registers
6.4.4.4
FC 04 - Read Input Registers
HB130 | CP | 341-1CH01 | en | 18-40
This function serves to read individual registers of the output area of the slave.
DB SEND source
Address
Name
+0.0
ADDR
+1.0
FUNC
+2.0
start_register
+4.0
register_number
n
start_register
start_register is not checked by the driver and is sent unchanged.
n
register_number
1...127 (ASCII: 1...125) registers (words) may be read.
DB RCV destination
Address
Name
+0.0
data[1]
+2.0
data[2]
...
...
This function serves to read individual registers of the input area of the slave.
DB SEND source
Address
Name
+0.0
ADDR
+1.0
FUNC
+2.0
start_register
+4.0
register_number
start_register
n
start_register is not checked by the driver and is sent unchanged.
n
register_number
1...127 (ASCII: 1...125) registers (words) may be read.
Communication protocols
Modbus > Modbus Master - Function codes
Type
Comment
BYTE
Slave address
BYTE
Function code
WORD
Register start address
INT
Amount of registers
Type
Comment
WORD
Data
WORD
Data
...
...
Type
Comment
BYTE
Slave address
BYTE
Function code
WORD
Register start address
INT
Amount of registers
61