YASKAWA CP 341 Manual page 101

Rs422/485
Table of Contents

Advertisement

VIPA System 300S
Event class 14 (0Eh) "Loadable Driver - General Processing Errors <Processing of a BSEND Job>"
Event class / number Description
0E 55h
0E 56h
0E 57h
0E 58h
0E 61h
0E 62h
0E 63h
0E 64h
0E 65h
0E 66h
0E 67h
HB130 | CP | 341-1CH01 | en | 18-40
With Modbus master only
The byte counter received in the reply message is wrong.
Remedy: Check slave device.
With Modbus master only
Echo wrong: The data of the reply message (amount of bits, ...) echoed from the slave are dif-
ferent from the data sent in the request message.
Remedy: Check slave device.
With Modbus master only
CRC check incorrect (Modbus Master ASCII: LRC check incorrect): An error has occurred on
checking the CRC (LRC) checksum of the reply message from the slave.
Remedy: Check slave device.
With Modbus master ASCII only
A received character within the reply message is not an ASCII character (0...9, A...F).
Remedy: Check slave device. Make sure it is in ASCII mode and not RTU.
With Modbus master only
Reply message with Exception Code 01: Illegal Function
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 02: Illegal Data Address
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 03: Illegal Data Value
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 04: Failure in associated device
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 05: Acknowledge
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 06: Busy, Rejected message
Remedy: See manual of slave device.
With Modbus master only
Reply message with Exception Code 07: Negative Acknowledgment
Remedy: See manual of slave device.