YASKAWA CP 341 Manual page 45

Rs422/485
Table of Contents

Advertisement

VIPA System 300S
Protocol parameter
Parameter
Character delay time
(ZVZ)
Acknowledgement
delay time (ADT)
Setup attempts
Transmission attempts This parameter defines the maximum number of attempts the CP is
Speed
Parameter
Baud rate in bit/s
HB130 | CP | 341-1CH01 | en | 18-40
The character delay time defines the maximum amount of time permitted between two
incoming characters within a message frame.
Description
Please regard the shortest character delay time depends on the baud rate:
Baud rate (bit/s)
300
600
1200
2400 ... 76800
n
Range of values: 20...65535ms in 10ms steps
The acknowledgment delay time defines the maximum amount of time per-
mitted for the partner's acknowledgment to arrive during connection setup
or release. Please regard the shortest ackno
Baud rate (bit/s)
300
600
1200
2400 ... 76800
n
Range of values: 20...65535ms in 10ms steps
This parameter defines the maximum number of attempts the CP is
allowed in order to establish a connection. After an unsuccessful attempt,
the procedure will be aborted and the error displayed in the STATUS output
of the FB.
n
Range of values: 1...255
allowed in order to transfer a message frame. After an unsuccessful
attempt, the procedure will be aborted and the error displayed in the
STATUS output of the FB.
n
Range of values: 1...255
Here the transfer speed may be selected from a selection list.
Description
Transfer speed in bit/s
n
Range of values: 300, 600, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 76800
ZVZ (ms)
60
40
30
20
QVZ (ms)
60
40
30
20
Communication protocols
3964(R) > 3964(R) - Parameter
Default value
220ms
2000ms
(550ms at 3964
without block
check)
6
6
Default value
9600
45