VIPA System 300S
Assembly possibilities
Approach
HB130 | CP | 341-1CH01 | en | 18-40
Please regard the allowed environment temperatures:
1
horizontal assembly: from 0 to 60°C
2
vertical assembly: from 0 to 40°C
3
lying assembly: from 0 to 40°C
If you do not deploy SPEED-Bus modules, the assembly happens with the following
approach:
1.
Bolt the profile rail with the background (screw size: M6), so that you still have min-
imum 65mm space above and 40mm below the profile rail.
2.
If the background is a grounded metal or device plate, please look for a low-impe-
dance connection between profile rail and background.
3.
Connect the profile rail with the protected earth conductor. For this purpose there is
a bolt with M6-thread.
4.
The minimum cross-section of the cable to the protected earth conductor has to be
2
10mm
.
5.
Stick the power supply to the profile rail and pull it to the left side to the grounding
bolt of the profile rail.
6.
Fix the power supply by screwing.
7.
Take a backplane bus connector and click it at the CPU from the backside like
shown in the picture.
8.
Stick the CPU to the profile rail right from the power supply and pull it to the power
supply.
9.
Click the CPU downwards and bolt it like shown.
10.
Repeat this procedure with the peripheral modules, by clicking a backplane bus
connector, stick the module right from the modules you've already fixed, click it
downwards and connect it with the backplane bus connector of the last module and
bolt it.
Assembly and installation guidelines
Assembly standard bus