5.4.3 Show CP firmware version

HB130 | CP | 341-1CH01 | en | 18-40
3.
You start the transfer of the firmware as soon as you tip the RUN/STOP lever down-
wards to MRES within 10s.
4.
During the update process, the LEDs SF and FRCE are alternately blinking and
MMC LED is on. This may last several minutes.
5.
The update is successful finished when the LEDs PWR, STOP, SF, FRCE and MCC
are on.
ð If they are blinking fast, an error occurred.
6.
Turn Power OFF and ON.
Now it is checked by the CPU, whether further current firmware versions are avail-
able at the MMC. If so, again the LEDs SF and FRCE flash after a short start-up
period. Continue with point 3.
ð The update is successful finished when the LEDs PWR, STOP, SF, FRCE and
MCC are on.
There is the possibility to display the current release of hard- and software of the CP by
means of the module information of the Siemens SIMATIC manager.
1.
Here go online to the corresponding CP in the hardware configurator by 'Station
è Open online'.
2.
If you use a SPEED7 CPU the current release of the firmware may be displayed by
the web page of the CPU as shown above.
Firmware update > Show CP firmware version