VIPA System 300S

4.2 Structure

CP 341-1CH01
RS422/485 interface
HB130 | CP | 341-1CH01 | en | 18-40
1
LED status indicators
The following components are under the front flap
2
RS422/485 interface
n
Pin compatible to Siemens CP 341 (6ES7 341-1CH01-0AE0)
n
Logical conditions as voltage difference between 2 twisted lines
n
Serial bus connection
Full-duplex: Four-wire operation (RS422)
Half-duplex: Two-wire operation (RS485)
n
Line length:
1200m at 19.2kbit/s
500m at 38.4kbit/s
250m at 76.8kbit/s
n
Data transfer rate up to 76.8kbit/s