CAN network
Pre-Operational
CAN network
Operational
CAN network
Stopped
State transitions
Below you will find a description of the state transitions in the "CANopen Manager" mode:
Transition
1
2
3
4
5
6, 7, 8
9, 10, 11, 12
SIMATIC PN/CAN LINK
Operating Instructions, 03/2018, A5E39895388-AB
All slaves connected via CANopen and the PN/CAN LINK are in the
"Pre-Operational" state.
All slaves connected via CANopen and the PN/CAN LINK are in the
"Operational" state.
All slaves connected via CANopen and the PN/CAN LINK are in the
"Stopped" state.
Meaning / trigger
Takes place as soon as the PN/CAN LINK is configured by the S7 controller for
the first time after booting.
Takes place automatically. A "Boot-Up" message is sent because the PN/CAN
LINK changes to NMT state "Pre-Operational".
Takes place when all configured "mandatory" CANopen slaves are available and
have been booted successfully.
Takes place when the control bit in the cyclic data from the S7 controller is set to
"ON". With this transition all CANopen slaves that are completely booted are set
to "Operational" by NMT.
Takes place when the control bit in the cyclic data from the S7 controller is set to
"OFF". With this transition all CANopen slaves that are completely booted are set
to "Pre-Operational" by NMT.
Is triggered by a heartbeat / node-guarding error of a "mandatory" slave if con-
figured accordingly (NMT Master error behavior is "Stop the PN/CAN LINK and
all nodes").
With this transition all CANopen slaves are set to "Stopped" by NMT.
Triggered by:
A heartbeat / node-guarding error of a "mandatory" slave if configured ac-
•
cordingly (NMT Master error behavior is "Restart of the PN/CAN LINK").
Reset bit contained in the cyclic data from the S7 controller
•
Reconfiguration by the S7 controller
•
Error during boot-up (except heartbeat/node-guarding errors)
•
Functions
4.1 CANopen