ABB Substation Automation
Products and Systems
3.
1MRS750886-MUM
User's Guide
Check lists
Table 48: Setting group 1
Variable
Start voltage of stage U>
Operate time of stage U>
Time multiplier k>
Drop-off/pick-up ratio D/P> of
stage U>
Start voltage of stage U>>
Operate time of stage U>>
Time multiplier k>>
Start voltage of stage U<
Operate time of stage U<
Time multiplier k<
Drop-off/pick-up ratio D/P< of
stage U<
Start voltage of stage U<<
Operate time of stage U<<
Time multiplier k<<
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Group 1
Setting range
(R, W, P)
S41
0.60...1.40 x U
n
S42
0.06...600 s
S43
0.05...2.00
S44
0.95...0.99
S45
0.80...1.60 x U
n
S46
0.05...600 s
S47
0.05...2.00
S48
0.30...1.20 x U
n
S49
0.10...600 s
S50
0.10...2.00
S51
1.01...1.05
S52
0.30...1.20 x U
n
S53
0.10...600 s
S54
0.10...2.00
S55
0...31
S56
0...255
S57
0...255
S58
0...63
S59
0...255
S60
0...15
S61
0...15
S62
0...15
S63
0...15
S64
0...15
S65
0...15
S66
0...15
S67
0...15
REU 513
Customer's
Default setting
setting
1.20 x U
n
0.06 s
0.05
0.97
1.20 x U
n
0.05 s
0.05
0.30 x U
n
0.10 s
0.10
1.03
0.30 x U
n
0.10 s
0.10
0
0
170
0
0
12
3
12
3
12
3
12
3
57