Check lists

Setting group 1
Variable
Start current of
stage I>
Operate time or time
multiplier k of stage I>
Start current of
stage I>>
Operate time of
stage I>>
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Group 1
Setting
(R, W, P)
range
S41
0.30...5.00 x I
S42
0.05...300 s
S43
0.30...35.0 x I
S44
0.04...300 s
S45
0...255
S46
0...255
S47
0...255
S48
0...255
S49
0...255
S50
0...255
S51
0...255
S52
0...255
ABB Substation Automation
Products and Systems
Default
Customer's
setting
0.30 x In
n
0.05 s /
0.05
0.30 x In
n
0.04 s
0
0
0
0
12
3
12
3
1MRS750613-MUM