ABB REU 513 User Manual page 55

Combined overvoltaqge and undervoltage relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750886-MUM
User's Guide
Table 45: Electromagnetic compatibility tests
Fast transient disturbance tests
• ac/dc ports
• Binary input
Surge immunity test
• Power supply, ac/dc ports
• I/O ports
Electromagnetic immunity tests
• Power frequency magnetic field
Voltage dips and short interruptions
Electromagnetic emission tests
• Conducted, RF-emission
(Mains terminal)
• Radiated RF-emission
CE approval
According to IEC 60255-22-4 and IEC 61000-4-4
4 kV
2 kV
According to IEC 61000-4-5
4 kV, common mode
2 kV, differential mode
2 kV, common mode
1 kV, differential mode
According to IEC 61000-4-8
100 A/m
According to IEC 61000-4-11
30 % / 10 ms
60 % / 100 ms
>95 % / 5000 ms
According to EN 55011 and EN 50081-2
EN 55011, class A
EN 55011, class A
Complies with the EMC directive 89/336/EEC
and the LV directive 73/23/EEC
REU 513
55