ABB REU 513 User Manual page 15

Combined overvoltaqge and undervoltage relay
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750886-MUM
User's Guide
Table 2: Fault codes
Fault
Type of fault
code
4
No response on output contact test, PO1
5
No response on output contact test, PO2
6
No response on output contact test, SO1
7
No response on output contact test, SO2
30
Faulty program memory (ROM)
50
Faulty work memory (RAM)
51
Parameter memory (EEPROM) faulty, block 1
52
Parameter memory (EEPROM) faulty, block 2
53
Parameter memory (EEPROM) faulty, blocks 1 and 2
54
Parameter memory (EEPROM) faulty, blocks 1 and 2 have different checksums
55
Parameter memory (RAM) faulty
56
Parameter memory (EEPROM) key faulty
59
Faulty work memory (RAM)
131
Reference voltage too low, 24V
139
Reference voltage too high, 24V
195
Reference voltage too low, +15V
203
Reference voltage too high, +15V
222
Reference voltage too low, -15V
223
Reference voltage too high, -15V
253
No interruptions from the A/D-converter
REU 513
15

Advertisement

Table of Contents
loading