REU 513
58
User's Guide
Table 49: Setting group 2
Variable
Start voltage of stage U>
Operate time of stage U>
Time multiplier k>
Drop-off/pick-up ratio D/P> of
stage U>
Start voltage of stage U>>
Operate time of stage U>>
Time multiplier k>>
Start voltage of stage U<
Operate time of stage U<
Time multiplier k<
Drop-off/pick-up ratio D/P< of
stage U<
Start voltage of stage U<<
Operate time of stage U<<
Time multiplier k<<
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Group 2
Setting range
(R, W, P)
S81
0.60...1.40 x U
n
S82
0.06...600 s
S83
0.05...2.00
S84
0.95...0.99
S85
0.80...1.60 x U
n
S86
0.05...600 s
S87
0.05...2.00
S88
0.30...1.20 x U
n
S89
0.10...600 s
S90
0.10...2.00
S91
1.01...1.05
S92
0.30...1.20 x U
n
S93
0.10...600 s
S94
0.10...2.00
S95
0...31
S96
0...255
S97
0...255
S98
0...63
S99
0...255
S100
0...15
S101
0...15
S102
0...15
S103
0...15
S104
0...15
S105
0...15
S106
0...15
S107
0...15
ABB Substation Automation
Products and Systems
Customer's
Default setting
setting
1.20 x U
n
0.06 s
0.05
0.97
1.20 x U
n
0.05 s
0.05
0.30 x U
n
0.10 s
0.10
1.03
0.30 x U
n
0.10 s
0.10
0
0
170
0
0
12
3
12
3
12
3
12
3
1MRS750886-MUM