REU 513
42
User's Guide
Recorded data
Parameter V1 indicates the highest and parameter V2 the lowest voltage value
measured as multiples of the rated voltage U
shows the average voltage value during one minute's time, updated once a minute.
The average voltage during a ten minutes' period is shown by parameter V4. The
value is updated for the first time ten minutes after the relay start-up and after that
once a minute. Parameters V5...V8 indicate the number of starts of the protection
stages, parameter V9 shows the operation indication code and parameter V10 the
stage that has tripped.
Table 21: Recorded data: Parameters V1...V10
Recorded data
Maximum voltage measured after reset
Minimum voltage measured after reset
Average voltage during 1 minute
Average voltage during 10 minutes
Number of starts of stage U>
Number of starts of stage U>>
Number of starts of stage U<
Number of starts of stage U<<
Operation indication code
Stage/voltage that caused tripping;
the value may also be a combination of
two or more of the individual values,
e.g. 24 (= 8 + 16)
ABB Substation Automation
Products and Systems
since the last reset. Parameter V3
n
Para-
R/W
Value
meter
V1
R
0...2 x U
V2
R
0...2 x U
V3
R
0...2 x U
V4
R
0...2 x U
V5
R
0...255
V6
R
0...255
V7
R
0...255
V8
R
0...255
V9
R
0 = ---
1 = starting of stage U>
2 = tripping of stage t>
3 = starting of stage U>>
4 = tripping of stage t>>
5 = starting of stage U<
6 = tripping of stage t<
7 = starting of stage U<<
8 = tripping of stage t<<
9 = tripping of CBFP unit
V10
R
1 = U
12
2 = U
23
4 = U
31
8 = U
12
16 = U
32 = U
64 = U
128 = U
256 = U
512 = U
1024 = U
2048 = U
4096 = U1s
n
n
n
n
>
>
>
>>
>>
23
>>
31
<
12
<
23
<
31
<<
12
<<
23
<<
31
1MRS750886-MUM