ABB REU 513 User Manual page 44

Combined overvoltaqge and undervoltage relay
Table of Contents

Advertisement

REU 513
44
User's Guide
Disturbance recorder
Table 23: M parameters for disturbance recorder
Description
Analogue channels in use
Digital channels in use
Sampling rate
Station identification/ unit
number
Rated frequency
Station name
Digital channel texts
Analogue channel texts
Analogue channel(s):
rated voltage and unit of
primary voltage
transformer(s)
Table 24: V parameters for disturbance recorder
Description
Internal trigger signals'
checksum
Internal trigger signal's
edge
External trigger signal
(BI signal)
External trigger signal's
edge
Post-triggering recording
length
Triggering state, clearing
and restart
Parameter
R/W
M13
R
M14
R
M15
R
M18
R/W
M19
R
M20
R/W
M40...47
R
M60...62
R
M80
R/W
Parameter
R/W
V241
R,W
V242
R,W
V243
R,W
V244
R,W
V245
R,W
V246
R,W
ABB Substation Automation
Products and Systems
Value/Note
7 (=00000111B)
255 (=11111111B)
800 or 960 Hz
0...9999
50 or 60 Hz
Max 15 characters
XXXX,YY;
where
XXXX: 0.00...600, YY: V or kV
(e.g. 20.0,kV)
Value
0...127, see table 25
0...127,
0=rising, 1=falling
0 / 1, see table 26
0 / 1,
0=rising, 1=falling
0...40, amount of periods
R:
0=recorder not triggered
1=recorder triggered and
recording stored into the
memory
W:
0=clear recorder memory
2=download restart; sets first
information and time stamp for
triggering ready to be read
4=manual triggering
1MRS750886-MUM

Advertisement

Table of Contents
loading