ABB REU 513 User Manual page 46

Combined overvoltaqge and undervoltage relay
Table of Contents

Advertisement

REU 513
46
User's Guide
Control parameters
Table 27: Control parameters
Description
Resetting of output contacts with
the latching feature
Resetting of registers and output
contacts with the latching feature
Rated frequency
Nominal voltage
Remote control of settings
Event mask for U> and U>>
Event mask for U< and U<<
Event mask for output contacts'
events
Event mask for disturbance
recorder
Entering the password for
settings
Changing the password or
reinstating password protection
Activating the self-supervision
READY LED
LED test for start and trip
indicators
Default settings
Internal fault code
SPA address of the relay
Data transfer rate, kbps
Relay serial number
CPU serial number
Hardware number
Test date
Para-
R/W
Value
meter
V101
W
1=reset
V102
W
1=reset
V133
R,W (P)
50=50 Hz
60=60 Hz
V134
R,W (P)
100, 110, 115, 120 (V)
V150
R,W
0=setting group 1
1=setting group 2
V155
R,W
0...255, see Event codes
V156
R,W
0...255, see Event codes
V157
R,W
0...255, see Event codes
V158
R,W
0 / 1, see Event codes
V160
W
1...999
V161
W (P)
1...999
V165
W
0=normal operation
1=self-supervision READY LED
blinking
V166
W (P)
0=start and trip LEDs off
1=trip LED on, start LED off
2=start LED on, trip LED off
3=start and trip LEDs on
V167
W (P)
2=Restore factory settings
V169
R
0...255
V200
R, W
1...254
V201
R, W
4.8 or 9.6
V230
R
ERxxxxxx
V231
R
MRxxxxxx
V232
R
1MRS090405-BAA
V233
R
YYYYMMDD
ABB Substation Automation
Products and Systems
1MRS750886-MUM

Advertisement

Table of Contents
loading