PRECISION DIGITAL ProVu PD6210 Instruction Manual

Analog input & pulse input batch controllers
Hide thumbs Also See for ProVu PD6210:
Table of Contents

Advertisement

Quick Links

P
RO
PD6210 Analog Input &
 PD6210: 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, 10 V Inputs
 PD6310: Pulse, Open Collector, NPN, PNP, TTL, Switch
Contact, Sine Wave (Coil), Square Wave Inputs
 NEMA 4X, IP65 Front
 Start/Pause/Stop, Change Batch with Front Panel Buttons
 Single or Multi-Stage Batch Control (Up to 8 Relays)
 Automatic Overrun Correction
 Rate in Units per Second, Minute, Hour, or Day
 Automatic or Manual Batch Control
 Low or High Flow Alarms
 9 Digit Grand Total with Overflow Feature
 Count Up or Down with Each Batch
 Free MeterView
and Programming
PRECISION DIGITAL CORPORATION
89 October Hill Road • Holliston MA 01746 USA
Tel (800) 343-1001 • Fax (508) 655-8990
V
Batch Controllers
U
PD6310 Pulse Input
®
Pro Software for Operation, Monitoring,
www.predig.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProVu PD6210 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PRECISION DIGITAL ProVu PD6210

  • Page 1  9 Digit Grand Total with Overflow Feature  Count Up or Down with Each Batch ®  Free MeterView Pro Software for Operation, Monitoring, and Programming PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com...
  • Page 2 Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages resulting from such improper use. Limited Warranty Precision Digital Corporation warrants this product against defects in material or workmanship for the specified period under “Specifica-...
  • Page 3: Table Of Contents

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Table of Contents INTRODUCTION ------------------------------------------------------------- 7 ORDERING INFORMATION ---------------------------------------------- 7 SPECIFICATIONS ----------------------------------------------------------- 9 General ------------------------------------------------------------------------------- 9 PD6210 Process Input -------------------------------------------------------- 11 PD6310 Pulse Input ------------------------------------------------------------ 11 Batch Controller Rate/Totalizer Display -------------------------------- 12 Relays ------------------------------------------------------------------------------ 13 Isolated 4-20 mA Transmitter Output ------------------------------------ 14 ®...
  • Page 4 Model PD6210 & PD6310 Batch Controllers Instruction Manual Control Menu (Contrl) -------------------------------------------------------- 42 Setting Up the Batch Controller (setup) -------------------------------- 43 Scaling and Calibration ----------------------------------------------------- 44 Setting the Input Signal (input) -------------------------------------------- 45 Setting the Totalizer and Batching Features (total) ---------------- 45 Setting the Decimal Point (dEc pt) -------------------------------------- 45 Programming the Rate/Totalizer (prog) -------------------------------- 46 Scaling the Controller (SCALE) ----------------------------------------- 47...
  • Page 5 Model PD6210 & PD6310 Batch Controllers Instruction Manual Grand Total Reset Password & Non-Resettable Total -------------- 67 Making Changes to a Password Protected Controller -------------- 67 Disabling Password Protection -------------------------------------------- 68 ADVANCED OPERATION AND PROGRAMMING --------------- 69 Advanced Features Menu & Display Messages ---------------------- 70 Programmable Function Keys User Menu (user) -------------------- 73 Multi-Point Calibration &...
  • Page 6 Model PD6210 & PD6310 Batch Controllers Instruction Manual Table of Figures Figure 1: 1/8 DIN Panel Cutout and Mounting ........18 Figure 2: Controller Dimensions - Side View ........19 Figure 3: Controller Dimensions - Top View ........19 Figure 4: Jumper Configuration for 12/24 VDC Power ..... 20 Figure 5: Transmitter Supply Voltage Selection .......
  • Page 7: Introduction

    Model PD6210 & PD6310 Batch Controllers Instruction Manual INTRODUCTION ® The P PD6210 and PD6310 are easy to use batch controllers ideal for simplifying independent batch control operations where local control is preferred to expensive and expansive plant operation systems. The controller comes programmed for easy front panel start, pause, stop, and batch size (preset) changes.
  • Page 8 Model PD6210 & PD6310 Batch Controllers Instruction Manual Pulse Input Standard Models 85-265 VAC 12/24 VDC Options Installed Model Model PD6310-6R2 PD6310-7R2 2 relays (PD1102*) PD6310-6R4 PD6310-7R4 4 relays (PD1104*) PD6310-6R5 PD6310-7R5 2 relays & 4-20 mA output (PD1105*) PD6310-6R7 PD6310-7R7 4 relays &...
  • Page 9: Specifications

    Model PD6210 & PD6310 Batch Controllers Instruction Manual SPECIFICATIONS Except where noted all specifications apply to operation at +25°C. General DISPLAY Main display: 0.6" (15 mm) high, red LEDs Second display: 0.46" (12 mm) high, red LEDs 6 digits: each (-99999 to 999999), with lead zero blanking. DEFAULT The main (Big) display shows batch total.
  • Page 10 Model PD6210 & PD6310 Batch Controllers Instruction Manual Three programmable passwords restrict modification of PASSWORD programmed settings and two prevent resetting the totals. Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
  • Page 11: Pd6210 Process Input

    Model PD6210 & PD6310 Batch Controllers Instruction Manual PD6210 Process Input INPUTS Field selectable: 0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave) ACCURACY ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span TEMPERATURE 0.005% of calibrated span/C max from 0 to 65C ambient,...
  • Page 12: Batch Controller Rate/Totalizer Display

    Model PD6210 & PD6310 Batch Controllers Instruction Manual INPUT Pulse input: Greater than 300 k @ 1 kHz. IMPEDANCE Open collector/switch input: 4.7 k pull-up to 5 V. ACCURACY ±0.03% of calibrated span ±1 count TEMPERATURE Rate display is not affected by changes in temperature. DRIFT MULTI-POINT 2 to 32 points...
  • Page 13: Relays

    Model PD6210 & PD6310 Batch Controllers Instruction Manual TOTALIZER Calculates total based on rate and field programmable mul- tiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed.
  • Page 14: Isolated 4-20 Ma Transmitter Output

    Model PD6210 & PD6310 Batch Controllers Instruction Manual RELAY Batch control OPERATION Automatic (non-latching) Sampling Off (disable unused relays and enable Interlock feature) Manual on/off control mode Secondary Functions Pump alternation control (2 to 8 relays) Latching (requires manual acknowledge) RELAY RESET User selectable via front panel buttons, digital inputs, or PC 1.
  • Page 15: Modbus ® Rtu Serial Communications

    Model PD6210 & PD6310 Batch Controllers Instruction Manual EXTERNAL LOOP 35 VDC maximum POWER SUPPLY OUTPUT LOOP Power supply Minimum Maximum RESISTANCE 24 VDC 10  700  35 VDC (external) 100  1200  ® Modbus RTU Serial Communications SLAVE ID 1 –...
  • Page 16: Compliance Information

    Model PD6210 & PD6310 Batch Controllers Instruction Manual COMPLIANCE INFORMATION Safety UL & c-UL LISTED USA & Canada UL 508 Industrial Control Equipment UL FILE NUMBER E160849 FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided LOW VOLTAGE EN 61010-1:2001 DIRECTIVE Safety requirements for measurement, control, and...
  • Page 17: Safety Information

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Note: Testing was conducted on PD6200 and PD6300 series meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance. All hardware is identical to the PD6210 and PD6310 controllers.
  • Page 18: Installation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual INSTALLATION There is no need to remove the controller from its case to com- plete the installation, wiring, and setup of the controller for most applications. Instructions are provided for setting up a 12/24 VDC powered controller to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 20.
  • Page 19: Figure 2: Controller Dimensions - Side View

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Mounting Dimensions 1.76" (45 mm) 2.45" (62 mm) 4.77" 0.59" (121 mm) (15 mm) 5.05" (128 mm) Figure 2: Controller Dimensions - Side View 4.17" (106 mm) 3.61" (92 mm) 4.68" (119 mm) Figure 3: Controller Dimensions - Top View...
  • Page 20: Configuration For 12 Or 24 Vdc Power Option

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Configuration for 12 or 24 VDC Power Option Do not exceed voltage rating of the selected configuration. Warning! Controllers equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC. To configure the controller for 12 VDC power: Remove all the connectors.
  • Page 21: Transmitter Supply Voltage Selection (P+, P-)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Transmitter Supply Voltage Selection (P+, P-) All controllers, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor. If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
  • Page 22: Connectors Labeling

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Connectors Labeling The connectors’ label, affixed to the controller, shows the location of all connectors available with requested configuration. Do not connect any equipment other than Precision Digital’s expansion modules, cables, or controllers to the RJ45 M-LINK connector.
  • Page 23: Pd6210 Signal Connections

    Model PD6210 & PD6310 Batch Controllers Instruction Manual PD6210 Signal Connections Signal connections are made to a five-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminal is the return for the 4-20 mA and the 10 V input signals. Current and Voltage Connections The following figures show examples of current and voltage connections.
  • Page 24: Figure 10: Voltage Input Connections

    Model PD6210 & PD6310 Batch Controllers Instruction Manual The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload. The fuse limits the current to a safe level when it detects a fault condi- tion, and automatically resets itself when the fault condition is removed.
  • Page 25: Pd6310 Signal Connections

    Model PD6210 & PD6310 Batch Controllers Instruction Manual PD6310 Signal Connections Signal connections are made to a five-terminal connector labeled SIGNAL on Figure 6. The COM (common) terminal is the return for the input signals. The following figures show examples of signal connections. Setup and programming is performed through the front panel buttons.
  • Page 26: Modbus Rtu Serial Communications

    Model PD6210 & PD6310 Batch Controllers Instruction Manual INPUT SIGNAL +5 V 4.7 k-ohm Internal pull-up PNP NPN LEVEL TYPE SENSOR Figure 11: NPN open Collector Input INPUT SIGNAL 4.7 k-ohm Internal pull-down PNP NPN LEVEL TYPE SENSOR Figure 12: PNP Sensor Powered by Internal Supply INPUT SIGNAL +5 V 4.7 k-ohm...
  • Page 27: Relay Connections

    Model PD6210 & PD6310 Batch Controllers Instruction Manual The same port is used for interfacing with all expansion modules (e.g. external relays, digital I/O). Use the PDA1200 controller copy cable for meter-to-meter interfacing for cloning purposes (i.e. copying settings from one controller to other con- trollers).
  • Page 28: 4-20 Ma Output Connections

    Figure 16: Low Voltage DC Loads Protection RC Networks Available from Precision Digital RC networks are available from Precision Digital and should be applied to each relay contact switching an inductive load. Part number: PDX6901. Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
  • Page 29: External Relay & Digital I/O Connections

    Model PD6210 & PD6310 Batch Controllers Instruction Manual External Relay & Digital I/O Connections The relay and the digital I/O expansion modules PDA1004 & PDA1044 are connected to the controller using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are iden- tical and interchangeable;...
  • Page 30: Interlock Relay Feature

    Model PD6210 & PD6310 Batch Controllers Instruction Manual DI 1-4 DO 1-4 5 VDC Figure 20: Digital I/O Module Connections Interlock Relay Feature As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay.
  • Page 31: Basic Operation And Programming

    Model PD6210 & PD6310 Batch Controllers Instruction Manual BASIC OPERATION AND PROGRAMMING The PD6210 is factory calibrated prior to shipment to read in mil- liamps and volts depending on the input selection. The calibration equipment is certified to NIST standards. The PD6310 has been factory calibrated to read input frequency in Hz (pulses/sec).
  • Page 32: Front Panel Buttons And Status Led Indicators

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Front Panel Buttons and Status LED Indicators Button Description Status Symbol Menu Relay 1 – 8 indicator START Rate indicator (Right arrow/F1) BATCH Batch Total indicator (Up arrow/F2) STOP Grand Total indicator (Enter/F3) Note: Total overflow...
  • Page 33: Controller Operation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Controller Operation The PD6210 controller is capable of accepting current (0-20 mA, 4-20 mA) and voltage signals (0-5 V, 1-5 V, 0-10 V,  10 V) and the PD6310 accepts pulses (e.g. ±40mV to ± 8V), square wave (0-5, 0-12V, or 0-24V), open collector NPN, PNP, TTL, or switch contact signals.
  • Page 34: Batch Control Operation Example

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Batch Control Operation Example The following example shows how two stage batch control functions with a PD6210 or PD6310. This setup will establish a 55 gallon preset for the batch, with a main valve (high flow) that will close at 45 gallons, and a trickle valve (low or restricted flow) that will close at 55 gallons.
  • Page 35 Model PD6210 & PD6310 Batch Controllers Instruction Manual Batch Control Operation 1. A new container is prepared for the batch. Both valves are closed. Note that the big display may show the batch total from the last batch. 2. The START button is pressed. Both valves open. The barrel begins to fill as the total being dispensed is displayed in the big window.
  • Page 36 Model PD6210 & PD6310 Batch Controllers Instruction Manual 36 36 36...
  • Page 37 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Functions and Messages The controller displays various functions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu. Display Parameter Action/Setting Description...
  • Page 38 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Dis 1 Display 1 Program display 1 value Inp 2 Input 2 Calibrate input 2 signal or program input 2 value (up to 32 points) Display 2 Program display 2 value (up to 32 points) Dis 2 Error Error, calibration not successful, check...
  • Page 39 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Act 1 Action 1 Set relay 1 action Auto Automatic Set relay for automatic reset A-man Auto-manual Set relay for automatic & manual reset any time Latching Set relay for latching operation (relays LatCH assigned to rate) Lt-CLr...
  • Page 40 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Relay goes to non-alarm condition when loop break is detected Analog output Enter the Analog output scaling menu Aout Display 1 Program display 1 value Dis 1 Output 1 Program output 1 value (e.g.
  • Page 41 Model PD6210 & PD6310 Batch Controllers Instruction Manual Main Menu Map The main menu consists of the most commonly used functions: Reset, Control, Setup , and Password .  Press Menu button when a batch is not running to enter Program- ming Mode then press the Up arrow button to scroll main menu.
  • Page 42: Setting Numeric Values

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting Numeric Values The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit value. The digit being changed is displayed brighter than the rest. Press and hold up arrow to auto-increment the display value.
  • Page 43: Setting Up The Batch Controller (Setup)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting Up the Batch Controller (setup) The Setup menu is used to select: Input signal the controller will accept Enable or disable totalizer and batching features Decimal point position Program menu for scaling or calibration Display parameter and intensity Relay operation 4-20 mA analog output scaling...
  • Page 44: Scaling And Calibration

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Scaling and Calibration It is very important to read the following information, before proceeding to program the controller:  There is no need to recalibrate the controller when first received from the factory. ...
  • Page 45: Setting The Input Signal (Input)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting the Input Signal (input) PD6210: Enter the Input menu to set up the controller to display current ( mA ) or voltage ( volt ) inputs. The current input is capable of accepting any signal from 0 to 20 mA. Select current input to accept 0-20 mA or 4-20 mA signals.
  • Page 46: Programming The Rate/Totalizer (Prog)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Programming the Rate/Totalizer (prog) It is very important to read the following information, before proceeding to program the controller: PD6210 :  The PD6210 is factory calibrated prior to shipment to read in mil- liamps and volts depending on the input selection.
  • Page 47: Scaling The Controller (Scale)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Scaling the Controller (SCALE) The process inputs (4-20 mA and  10 VDC) can be scaled to display the process variable in engineering units. A signal source is not needed to scale the controller; simply program the inputs and corresponding display values.
  • Page 48: Time Base, Total Conversion Factor & Total Reset

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Time Base, Total Conversion Factor & Total Reset The time base, total conversion factor, and total reset menus are located in the Program menu. The total and grand total have their own independent settings. This means that one can be displaying the value in gallons while the other displays in million gallons, liters, m , etc.
  • Page 49: Calibrating The Controller With External Source (Cal)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Calibrating the Controller with External Source (Cal) To scale the controller without a signal source refer to Scaling the Controller ( SCALE ) page 47. The controller can be calibrated to display the process variable in engi- neering units by applying the appropriate input signal and following the calibration procedure.
  • Page 50: Setting The Display Parameter & Intensity (Dsplay)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting the Display Parameter & Intensity (dsplay) The main display ( Big ) can be programmed to display: Rate value Total or grand total Relay set points Max & min values Modbus input Display rate and units The small display ( Little ) can be programmed to display: Rate value...
  • Page 51: Display Setup Menu

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Setup Menu After setting up the input and the display, press the Menu button to exit programming and skip the rest of the setup menu. Press the Menu but- ton again and the Up arrow to reach the Program menu and complete the scaling or calibration of the meter.
  • Page 52: Character Set For Engineering Units Display (D Unit)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Character Set for Engineering Units Display (d unit) The small display can be programmed to show engineering units or cus- tom legends using the following 7-segment character set: Display Character Display Character Space Degree The letters “m”...
  • Page 53: Setting The Relay Operation (Relay)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting the Relay Operation (relay) This menu is used to set up the operation of the relays. CAUTION! During setup, the relays do not follow the input and they will remain in the state found prior to entering the Relay menu. Relay assignment Rate for low and high alarm Total for batch control relays...
  • Page 54: Relay Assignment (Assign)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual relay setup Assign Failsf delay break relay relay relay relay relay Asign1 break1 A s s i g n r l y 1 F a i l s f delay b r e a k ignore rly 1 F l s 1...
  • Page 55: Setting The Relay Action

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting the Relay Action Operation of the relays is programmed in the Action menu. The relays are commonly set up for any of the following modes of operation: Always set to Auto for Batch control operation. Also for automatic reset (non-latching) of alarms.
  • Page 56: Programming Alarm Set And Reset Points

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Programming Alarm Set and Reset Points High alarm indication: program set point above reset point. Low alarm indication: program set point below reset point. The deadband is determined by the difference between set and reset points.
  • Page 57: Relay Operation Details

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Relay Operation Details Overview The relays of the controller can serve two roles, as batch control relays for single or multi-stage batching, as rate, or grand total alarm, or as a sampling relay based on grand total or rate alarm. These capabilities include front panel alarm status LEDs and 2 or 4 in- ternal relays and/or 4 external relays expansion module.
  • Page 58: Front Panel Leds

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Front Panel LEDs The LEDs on the front panel provide status indication for the following: Status Status Alarm 1 Alarm 5 Alarm 2 Alarm 6 Alarm 3 Alarm 7 Alarm 4 Alarm 8 The controller is supplied with four alarm points that include front panel LEDs to indicate alarm conditions.
  • Page 59: Setting Up The Interlock Relay (Force On) Feature

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting Up the Interlock Relay (Force On) Feature Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature: 1. Access the Setup – Relay – Assign the relay to grand total . setup relay rly 1...
  • Page 60: Sample Relay Operation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Sample Relay Operation The sampling function allows the operator to set a set point for a “sam- pling” relay. This can be done for the rate or the grand total. Each time the relay reaches the set point, it will close that relay’s contacts for a programmed period of time A rate sampling relay will activate for the sample time ( sam t ), up to...
  • Page 61: High Alarm With Fail-Safe Operation (Set > Reset)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual High Alarm with Fail-Safe Operation (Set > Reset) Input Reset de-energized energized Relay Automatic (non-latching) Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state. Low Alarm with Fail-Safe Operation (Set <...
  • Page 62: Total Relay Sampling Operation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual When the signal crosses the set point, the relay trips and the sample time starts. After the sample time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high alarms and going down for low alarms.
  • Page 63: Signal Loss Or Loop Break Relay Operation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Signal Loss or Loop Break Relay Operation The following graph shows the loop break operation for a high alarm relay. Input Reset de-energized energized Relay Loop Break = Ignore Relay Loop Break = Off Relay Loop Break = On When the controller detects a break in the 4-20 mA loop, the relay will go...
  • Page 64: Time Delay Operation

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Time Delay Operation The following graphs show the operation of the time delay function. Input Reset <Tdelay <Tdelay >=Tdelay Relay On Time Delay Input Reset <Tdelay <Tdelay >=Tdelay Relay Off Time Delay When the signal crosses the set point, the On time delay timer starts and the relay trips when the time delay has elapsed.
  • Page 65: Scaling The 4-20 Ma Analog Output (Aout)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Scaling the 4-20 mA Analog Output (Aout) The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range selected. No equipment is needed to scale the analog output; simply program the display values to the corresponding mA output signal.
  • Page 66: Setting Up The Password (Pass)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Setting Up the Password (pass) The Password menu is used for programming three levels of security to prevent unauthorized changes to the programmed parameter settings and to program the non-resettable totalizer. Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
  • Page 67: Grand Total Reset Password & Non-Resettable Total

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Grand Total Reset Password & Non-Resettable Total The grand total can be password-protected to prevent unautho- rized total resets. The grand total can be programmed as a non-resettable total by entering the password “050873”. Once the Grand Total has been programmed as “non- resettable”...
  • Page 68: Disabling Password Protection

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Disabling Password Protection To disable the password protection, access the Password menu and enter the correct password twice, as shown below. The controller is now unprotected until a new password is entered. Run Mode 20.000 Locd...
  • Page 69: Advanced Operation And Programming

    Model PD6210 & PD6310 Batch Controllers Instruction Manual ADVANCED OPERATION AND PROGRAMMING In addition to the functions described in Controller Operation on page 33, the following advanced operation and display features may be pro- grammed. Configuring these features may disable some default batch controller features, or make running a batch operation impossible.
  • Page 70: Advanced Features Menu & Display Messages

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Advanced Features Menu & Display Messages The following table shows the functions and messages of the Advanced Features menu in the order they appear in the menu. Display Parameter Action/Setting filtr Filter Set noise filter value bypASs Bypass...
  • Page 71 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Program mA output for display overrange O-rang Overrange u-rang Underrange Program mA output for display underrange Loop Break Set relay condition if loop break detected Break Force output Force analog output value for loop break Force Ignore Ignore loop break condition...
  • Page 72 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Send controller settings to another control- send Send Done Copy function completed done Diagnostics Display parameter settings Diag Input Input selection Input Set noise filter level Filter Filter Set filter bypass level bypass Bypass Functn...
  • Page 73: Programmable Function Keys User Menu (User)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Function Keys Operation During operation, the programmable function keys operate according to the way they have been programmed in the Advanced Features – User menu. The following table shows the default setting for each of the func- tion keys.
  • Page 74: Multi-Point Calibration & Scaling

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Function Keys & Digital I/O Available Settings Display Description Display Description Start batch GT on little display Start Lit gt Pause/stop batch Batch count display stop Lit bc Start/stop combo Disable input/button srtstp disabl Disable all relays...
  • Page 75 Model PD6210 & PD6310 Batch Controllers Instruction Manual In order to operate or program the batch controller using a computer, the controller must be connected using a USB, RS-232, or RS-485 serial adapter, see Accessories on page 8 for details. Maximum/Minimum Readings The max &...
  • Page 76: Noise Filter Bypass (Bypass)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Total and Grand Total Count Direction (Count) By default, the batch total and grand total count up during batch processes. Count parameter allows this to change. When set to count down, the batch total will count down from the preset to 0. When set to count down, the grand total will count down from a set value up to 999,999.
  • Page 77: Modbus Rtu Serial Communications (Serial)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Modbus RTU Serial Communications (serial) The controller is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol. To communicate with a computer or other data terminal equipment, an RS-232.
  • Page 78: Select Menu (Select)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Select Menu (SElEct) The Select menu is used to select the signal input conditioning applied to the input (linear, square root, or programmable exponent, low-flow cutoff, and analog output programming. The multi-point linearization is part of the linear function selection.
  • Page 79 Model PD6210 & PD6310 Batch Controllers Instruction Manual Square Root Linearization (Square) The square root function can be used to linearize the signal from a diffe- rential pressure transmitter and display flow rate in engineering units. Programmable Exponent Linearization (Prog E) The programmable exponent can be used to linearize the signal from level transmitters in open-channel flow applications using weirs and flumes.
  • Page 80: Analog Output Programming (Aoutpr)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Analog Output Programming (AoutPr) The Analog Output Programming menu is used to program the behavior of the 4-20 mA output. The following parameters and functions are pro- grammed in this menu: Source: Source for generating the 4-20 mA output (e.g. PV) Overrange: Analog output value with display in overrange condition Underrange: Analog output value with display in underrange condition Break: Analog output value when loop break is detected...
  • Page 81: Pd6210 Only: Internal Source Calibration (Ical)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual PD6210 Only: Internal Source Calibration (ICAL) Note: The PD6210 is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards. The internal source allows the user to scale the controller without apply- ing a signal.
  • Page 82 Model PD6210 & PD6310 Batch Controllers Instruction Manual Set the display value to correspond to the input signal being cali- brated, typically 4.000 mA. The display moves to the high input calibration ( C Hi ). Apply the high input signal and press Enter. Set the display for the high input calibration, in the same way as it was set for the low input calibration, typically 20.000 mA.
  • Page 83 Model PD6210 & PD6310 Batch Controllers Instruction Manual Error Message (Error) An error message indicates that the calibration or scaling process was not successful. After the error message is displayed, the controller reverts to input 2 dur- ing calibration or scaling and to input 1 during internal calibration, allow- ing the appropriate input signal to be applied or programmed.
  • Page 84: Controller Copy Function (Copy)

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Controller Copy Function (Copy) The Copy function is used to copy (or clone) all the settings from one controller to other controllers requiring exactly the same setup and pro- gramming ( i.e . type of input, scaling, decimal point, filter, bypass, etc.). Only the PDA1200 meter copy cable must be used for meter-to-meter interfacing.
  • Page 85 Model PD6210 & PD6310 Batch Controllers Instruction Manual Controller Copy or Cloning Instructions Do not connect the two controllers to the same signal source while cloning. Internal calibration may be affected. Caution! Connect two controllers using a PDA1200 controller copy cable. Use PDA1200 controller cable only! Using standard CAT5 or other cable will cause damage to both controllers.
  • Page 86: Troubleshooting

    Model PD6210 & PD6310 Batch Controllers Instruction Manual TROUBLESHOOTING The rugged design and the user-friendly interface of the controller should make it unusual for the installer or operator to refer to this section of the manual. However, due to the many features and functions of the control- ler, it’s possible that the setup of the controller does not agree with what an operator expects to see.
  • Page 87: Reset Controller To Factory Defaults

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Reset Controller to Factory Defaults When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults. Instructions to load factory defaults: Enter the Advanced Features menu.
  • Page 88: Factory Defaults & User Settings

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Factory Defaults & User Settings The following table shows the factory setting for the major programmable parameters on the controller. Next to the factory setting, the user may record the new setting for the particular application. Model: ______________ S/N: _______________ Date: _________ Parameter...
  • Page 89 Model PD6210 & PD6310 Batch Controllers Instruction Manual Parameter Display Default Setting User Setting Grand total time Second GT tb base Grand total 1.000 T CF conversion factor Grand total reset Manual T rst Relay 1 assignment Total Asign1 Relay 2 assignment Total Asign2 Relay 2 preclose...
  • Page 90 Model PD6210 & PD6310 Batch Controllers Instruction Manual Parameter Display Default Setting User Setting Off delay relay 1 0.0 sec Off 1 On delay relay 2 0.0 sec On 2 Off delay relay 2 0.0 sec Off 2 On delay relay 3 0.0 sec On 3 Off delay relay 3...
  • Page 91 Model PD6210 & PD6310 Batch Controllers Instruction Manual Parameter Display Default Setting User Setting Minimum output 0.000 mA Slave ID (Address) Slave Id Baud rate 9600 baud Transmit delay 10 ms Tr dly Parity Even Parity Byte-to-byte timeout 010 (0.1 sec) t-byt F1 function key Reset max &...
  • Page 92: Troubleshooting Tips

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Troubleshooting Tips Symptom Check/Action Check power at power connector No display at all Controller is password-protected, enter Not able to change setup or pro- correct six-digit password to unlock gramming, Locd is displayed Check: Controller displays error message Signal connections...
  • Page 93: Alphabetical List Of Display Functions & Messages

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Alphabetical List of Display Functions & Messages Display Parameter Action/Setting Description 20 mA output Enter mA output value read by milliamp 20 mA meter with at least 0.001 mA resolution 4 mA 4 mA output Enter mA output value read by milliamp meter with at least 0.001 mA resolution...
  • Page 94 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Current Calibrating 4-20 mA current input (internal C CAL reference source used for scaling the input) calibration C Hi Current high Calibrate high current input (e.g. 20 mA) Current low Calibrate low current input (e.g.
  • Page 95 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Diagnostics Display parameter settings Diag Display Set display intensity level from 1 to 8 d-Inty intensity Display 1 Program display 1 value Dis 1 Display 2 Program display 2 value Dis 2 Disable function key disabl...
  • Page 96 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Grand total reset Program grand total reset mode: auto or GT rst manual GT tb Grand total time Program grand total time base base Grand total Set or enter password for manual reset Gtotal password ICal...
  • Page 97 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Maximum Program maximum mA output allowed Modbus Select to display Modbus input or to assign mbus Modbus input as the analog output source Menu button Assign digital input to Menu button menu Minimum Program minimum mA output allowed...
  • Page 98 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Relay Enter the Relay menu RELaY Reset To access the Reset menu reset Right arrow Assign digital input to Right arrow button/F1 Right RLY 1 Relay 1 Relay 1 setup RLY 2 Relay 2 Relays 2-8 setup...
  • Page 99 Model PD6210 & PD6310 Batch Controllers Instruction Manual Display Parameter Action/Setting Description Start Begin batch Start Stop Pause/Stop batch Stop Reset tare Reset tare Tarest T CF Total conversion Program total conversion factor factor Time delay Program time delay for total auto reset T dly Total reset Program total reset mode: auto or manual...
  • Page 100 Model PD6210 & PD6310 Batch Controllers Instruction Manual NOTES...
  • Page 101: Figure 23: 1/8 Din Panel Cutout Template

    Model PD6210 & PD6310 Batch Controllers Instruction Manual Figure 23: 1/8 DIN Panel Cutout Template...
  • Page 102 Model PD6210 & PD6310 Batch Controllers Instruction Manual...
  • Page 103 Model PD6210 & PD6310 Batch Controllers Instruction Manual NOTES...
  • Page 104 Model PD6210 & PD6310 Batch Controllers Instruction Manual How to Contact Precision Digital  For Technical Support please Call: (800) 610-5239 or (508) 655-7300 Fax: (508) 655-8990 Email: support@predig.com  For Sales Support or to place an order please contact your local distributor or...