(Optional) Ec Motor - Daikin Enfinity CCW Installation And Maintenance Manual

Horizontal water source heat pumps
Table of Contents

Advertisement

Unit Size 060 (380/50/3, 460/60/3,
575/60/3)
The fan motor on unit size 060 for voltages 380/50/3,
460/60/3 and 575/60/3
(Figure
terminal block and are factory wired for high speed. Low
speed can be achieved by interchanging black terminal
(3) with red terminal (5) and the black and blue terminals
(3 & 4) receive a jumper as shown in
Figure 29: Size 060 (380/50/3, 460/60/3, 575/60/3 factory
wired for high speed
GRN
FAN MOTOR
Figure 30: Size 060 (380/50/3, 460/60/3, 575/60/3 low speed
GRN
FAN MOTOR
Unit Size 070 (208-230/60/3)
The fan motor on unit size 070 in voltage 208-230/60/3
has a four-position terminal block and is factory wired for
high speed
(Figure
31). Low speed can be achieved by
interchanging black terminal (3) with red terminal
Figure 31: Sizes 070 (208-230/60/3)
GR / YE
FAN MOTOR
www.DaikinApplied.com
29) have a five-position
Figure
30.
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
LINE
4 (BLU)
5 (RED)
HIGH SPEED
FACTORY WIRED
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
JUMPER LEAD
4 (BLU)
5 (RED)
LINE
LOW SPEED
(4).
LINE
1 (YEL)
CAPACITOR
2 (BRN)
HIGH
3 (BLK)
FACTORY
4 (RED)
WIRED
LOW
Unit Size 070 (460/60/3, 575/60/3)
The fan motor on unit size 070 for voltages 460/60/3 and
575/60/3
(Figure
32) have a five-position terminal block
and are factory wired for high speed. Low speed can be
achieved by interchanging black terminal (3) with red
terminal (5) and the black and blue terminals (3 & 4)
receive a jumper as shown in
Figure 32: Size 070 (460/60/3, 575/60/3) factory wired for
high speed
GRN
FAN MOTOR
Figure 33: Size 070 (460/60/3, 575/60/3 low speed
GRN
FAN MOTOR
Notes: All motors have a wiring label that is keyed for
proper wiring operation. Check unit wiring dia-
gram (on electrical access panel) for proper unit
operation. Not all labels are the same.
Units leaving the factory are wired for high or low
fan speed (see
speed settings).
Label is located on the back of the terminal block.

(Optional) EC Motor

The EC motor will maintain the rated airflow as static
pressure increases or decreases within the unit's
operating range. If an alternate airflow setting is required
call 800-432-1342.
25
P
t
s
rior
o
Figure
33.
1 (YEL)
CAPACITOR
2 (BRN)
3 (BLK)
4 (BLU)
5 (RED)
HIGH SPEED
FACTORY WIRED
1 (YEL)
CAPACITOR
2 (BRN)
3 (BLK)
JUMPER LEAD
4 (BLU)
5 (RED)
LOW SPEED
Table 10 on page 23
for fan
-
tart
uP
LINE
LINE
LINE
LINE
IM 1049-9