Daikin Enfinity CCW Installation And Maintenance Manual page 17

Horizontal water source heat pumps
Table of Contents

Advertisement

Table 5: MicroTech III unit controller terminals locations
and descriptions
H1 – 1
24
24 VAC Power Input
H1 – 2
C
24 VAC common
H2 – 1
SL1
Fan Low Speed Output – Switched L1
H2 – 2
Blank Terminal
H2 – 3
N
Fan Low Speed Output – Neutral
H3 – 1
HP1-1
Comp High Pressure Switch (HP1) Input Terminal 1
H3 – 2
HP1-2
Comp High Pressure Switch (HP1) Input Terminal 2
H4 – 1
1
Discharge Air Temp Sensor – Common
H4 – 2
Discharge Air Temp Sensor – Signal
H4 – 3
Leaving Water Temp Sensor – Common
H4 – 4
Leaving Water Temp Sensor – Signal
H5 – 1
1
I/O Expansion Module Common (Gnd)
H5 – 2
I/O Expansion Module Common (Gnd)
H5 – 3
I/O Expansion Module +5 VDC
H5 – 4
I/O Expansion Module SPI CE1
H5 – 5
I/O Expansion Module SPI CLK
H5 – 6
I/O Expansion Module SPI OUT
H5 – 7
I/O Expansion Module SPI IN
H5 – 8
I/O Expansion Module +12 VDC
H5 – 9
I/O Expansion Module 24 VAC
H5 – 10
I/O Expansion Module 24 VAC
H5 – 11
No Connection
H5 – 12
No Connection
H6 – 1
1
Condensate Overflow Signal Input
H6 – 2
Comp#1 Suction Temp Sensor (LT1) – Common
H6 – 3
Comp#1 Suction Temp Sensor (LT1) – Signal
H6 – 4
Comp#1 Low Pressure Switch (LP1) – Source Voltage
H6 – 5
Comp#1 Low Pressure Switch (LP1) – Signal
H6 – 6
Reversing Valve#1 – Common
H6 – 7
Reversing Valve#1 – Output
H7 – 1
1
No Connection
Table 6: MicroTech III Controller Configuration Jumper Settings
Baseboard Description
Normal / Test Mode
Fan Operation
Loop Fluid
Alarm "A" Terminal Output Polarity
Room Sensor Setpoint
Potentiometer Range
Thermostat / Room Sensor
Not Used
Not Used
Proper antifreeze/water solution is required to minimize the potential of fluid freeze-up. Jumper JP3 is factory set for water freeze protection with the jumper open. Operation with anti-freeze
protection requires JP3 to be field configured for the jumper closed. If unit is employing a fresh water system (no anti-freeze protection), it is extremely important that JP3 jumper setting
remains in the open position (factory default setting) in order to shut down the unit at the appropriate water temperature to protect your heat pump from freezing. Failure to do so can result
in unit damage and fluid leaks."
www.DaikinApplied.com
Jumper(s)
Jumper Setting
Open
JP1
Shorted
Open
JP2
Shorted
Open
JP3
(see warning)
Shorted
Open
JP4
Shorted
Open
JP5
Shorted
Open
JP6
Shorted
JP7
Open
JP8
Open
WARNING
17
H7 – 2
No Connection
H7 – 3
Red LED Output
H7 – 4
Green LED Output
H7 – 5
Yellow LED Output
H7 – 6
Red-Green-Yellow LED Common
H8 – 1
1
Isolation Valve/Pump Request Relay N/O
H8 – 2
Isolation Valve/Pump Request Relay N/C
H8 – 3
24 VAC Common
H9 – 1
1
Room Temp Sensor & Tenant Override – Signal
H9 – 2
Room Temp Sensor & Tenant Override – Common
TB1 – 1
1
Room Sensor – Status LED Output
TB1 – 2
2
Room Sensor – Fan Mode & Unit Mode Switches
TB1 – 3
3
Room Sensor – Setpoint Adjust
TB1 – 4
4
Room Sensor – Room Temp Sensor & Tenant Override
TB1 – 5
5
Room Sensor – DC Signal Common
TB2 – 1
R
24 VAC
TB2 – 2
A
Alarm Output
TB2 – 3
W2
Thermostat – Heat Stage #2 Input
TB2 – 4
W1
Thermostat – Heat Stage #1 Input
TB2 – 5
Y2
Thermostat – Cool Stage #2 Input
TB2 – 6
Y1
Thermostat – Cool Stage #1 Input
TB2 – 7
G
Thermostat – Fan Input
TB2 – 8
O
Thermostat – Tenant Override Input
TB2 – 9
C
24 VAC Common
TB3 – 1
E
Emergency Shutdown Input
TB3 – 2
U
Unoccupied/Occupied Input
L1 – 1
L1 - 1
Line Voltage Terminal 1
L1 – 2
L1 - 2
Line Voltage Terminal 2
L1 – 3
L1 - 3
Line Voltage Terminal 3
N1
N1
Neutral Terminal 1
N2
N2
Neutral Terminal 2
N3
N3
Neutral Terminal 3
SWL1
Switch – L1 Voltage
COMP
Relay
L1
No Connection
Function
Normal Operation
Service / Test Mode
Continuous Fan Operation (On), when not operating in the unccupied mode.
Cycling Fan Operation (Auto)
Water freeze protection (factory default setting)
Systems with anti-freeze protection
Fault de-energizes alarm output to 0VAC.
Fault energizes alarm output to 24VAC.
Short Range: -3 to +3 ºF (-1.67 to +1.67 ºC)
Long Range: 55 to 95 ºF (12.78 to 35 ºC)
Thermostat Control
Room Sensor Control
C
ontrols
IM 1049-9