Microtech Iii Controller With Bacnet® Communication; Module - Daikin Enfinity CCW Installation And Maintenance Manual

Horizontal water source heat pumps
Table of Contents

Advertisement

MicroTech III Controller with
BACnet® Communication Module
For installation and operation information on MicroTech
III unit controller and other ancillary components, see:
IM 928 - MicroTech III BACnet Communication

Module

OM 931 - MicroTech III Unit Controller for Water
Source Heat Pumps Operation and Maintenance
Manual
IM 955 - MicroTech III Wall Sensor For use with
Microtech III Unit Controller
Daikin water source heat pumps are available with
Daikin BACnet MS/TP communication module that
is designed to communicate over a BACnet MS/TP
communications network to a building automation
system (BAS). It can be factory or field-installed.
The unit controller is programmed and tested with all the
logic required to monitor and control the unit. An optional
wall sensor may be used with the communication
module to provide limited local control of the water
source heat pump. The unit controller monitors water
and air temperatures and passes information to the
communication module. The module communicates with
the BAS, to provide network control of the water source
heat pump.
The module makes operational data and commands
available on a communications network using BACnet
objects and properties:
The network cable is a shielded twisted-pair cable
Network communications run up to 76.8 Kbps
DIP switches on the controller enable the MS/TP
MAC address to be set in the range 0-127
NOTICE
When installing a MicroTech III Horizontal unit size 007, 009
or 012 which are provided with a factory-mounted BACnet
communication module, it is suggested that the MAC address dip
switches on the communication module be set prior to installing
the unit in the ceiling. Access to the dip switches may be limited
when the unit is installed. Reference IM 928 for addressing
methods available.
Four green status LEDs on the communication
module indicate communication activity on the
MS/TP communication network and with the unit
controller
www.DaikinApplied.com
Figure 17: MicroTech III BACnet Water Source Heat Pump
Snap-in Communication Module
MicroTech III Unit Controller with BACnet MS/TP
Communication Module orchestrates the following unit
operations:
Enable heating and cooling to maintain setpoint
based on a room sensor
Enable fan and compressor operation
Monitors all equipment protection controls
Monitors room and discharge air temperatures
Monitors leaving water temperature
Relays status of all vital unit functions
The MicroTech III unit controller with
communication module includes:
Return Air Temperature sensor (RAT)(field-installed)
Discharge Air Temperature sensor (DAT)(field-
installed)
Leaving Water Temperature sensor (LWT) (factory
installed)
Note: Refer to IM 956-X for details to install (RAT) &
(DAT) sensors.
When an optional wall-mounted room temperature sensor is
connected to the unit controller, the Return Air Temperature (RAT)
sensor must not be installed. A wall-mounted room temperature
sensor and the return air temperature sensor must not be
connected simultaneously or the unit will not operate properly.
The communication module provides access to setpoints
for operational control
Available wall sensors include:
Room sensor with LED status and tenant override
button
Room sensor with LED status, tenant override
button, and ±3°F setpoint adjustment
Room sensor with LED status, tenant override
button, 55° to 95°F setpoint adjustment
21
C
CAUTION
ontrols
IM 1049-9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Enfinity cch

Table of Contents