Standard Range Units - Daikin Enfinity CCW Installation And Maintenance Manual

Horizontal water source heat pumps
Table of Contents

Advertisement

Typical water source heat pump common design temperatures
Table 2: Typical water source heat pump common design temperatures
Operating
Minimum
Mode
DB
Cooling
75
Heating
60
Water source heat pump operating temperature limits (for continuous duty)
Table 3: Water source heat pump operating temperature limits (for continuous duty)
Operating
Minimum
Mode
DB
Cooling
65
Ambient
50
Heating
50
Ambient
50
Notes: In the heating mode, the sum of the entering air + entering water must be ≥ 100°F. MINIMUM WATER FLOW =
1.5 GPM/Ton. Maximum and minimum values may not be combined. If one value is at maximum or minimum, the
other two conditions may not exceed the normal condition for standard units. Extended range units may combine
any two maximum conditions, but not more than two, with all other conditions being normal conditions.
Water source heat pump operating temperature limits at start-up (not for continuous duty)
Table 4: Water source heat pump operating temperature limits at start-up (not for continuous duty)
Operating
Minimum
Mode
DB
Cooling
50
Ambient
45
Heating
40
Ambient
40

Standard Range Units:

Units are designed to start in an ambient of 50°F (10°C)
with entering air at 50°F (10°C), with entering water at
50°F (10°C), with nominal air flow and water flow (3.0
GPM/Ton), for initial start-up in heating.
Note: This is not a normal or continuous operating
condition. It is assumed that such start-up is for
the purpose of bringing the building space up to
occupancy temperature.
Geothermal Range Units:
Units are designed to start in an ambient of 40°F (5°C)
with entering air at 40°F (5°C), with entering water at
20°F (-7°C), with nominal air flow and water flow (3.0
GPM/Ton), for initial start-up in heating.
Note: This is not a normal or continuous operating
condition. It is assumed that such start-up is for
the purpose of bringing the building space up to
occupancy temperature.
www.DaikinApplied.com
Entering Air °F
Maximum
WB
DB
WB
63
80
70
Entering Air °F
Maximum
WB
DB
WB
55
85
100
80
85
Entering Air °F
Maximum
WB
DB
WB
40
105
110
85
85
Standard Range
Minimum
Maximum
67
85
100
60
70
Standard Range
Minimum
Maximum
71
55
110
55
90
Standard Range
Minimum
Maximum
87
45
120
40
95
Environment
This equipment is designed for indoor installation
only. Sheltered locations such as attics, garages, etc.,
generally will not provide sufficient protection against
extremes in temperature and/or humidity, and equipment
performance, reliability, and service life may be
adversely affected.
Power supply
A voltage variation of +/-10% of nameplate voltage is
acceptable. Three-phase system imbalance shall not
exceed 2%.
15
o
Perating
Entering Water °F
Extended Range
Minimum
Maximum
85
100
40
70
Entering Water °F
Extended Range
Minimum
Maximum
50
110
20
90
Entering Water °F
Extended Range
Minimum
Maximum
30
120
20
100
l
iMits
IM 1049-9